FIRECLASS Fire Alarm Control Panels 2.1 FIM Pseudo Points
Fault Finding Guide Doc. version 2 7
44 Inhibit Sound LED The system monitors the isolation status of sounder devices.
If all sounders are isolated, this point is set. Once one sounder is availa-
ble, the point is cleared.
The activation of this point inhibits the activation of the sounder LED.
The goal is not to indicate that sounders are active on the front panel,
when the system knows they are all isolated.
45 Commissioning The system monitors the commissioning states. If any are active, this
point is raised.
46 Download Required In network configurations, all panels broadcast details which relate to
their core functionality. If this differs between panels then the network
will not operate as intended and a full upload may not be possible.
47 Test Equipment This point is activated when FIRECLASS Checker is connected to the
panel.
48 Walktest Outputs This point is activated when an output test is started from the panel user
interface.
49–53 Not used
54 Force Day Mode If the panel is in day mode and a panel restart is performed. This point is
activated to return to panel to day mode.
55 Not used
56 Isolation For Test This point is activated if the menu option to isolate non-LED outputs is
selected.
57 Not used
58 FCExpress Download This point is activated while a download from Express is active on the
panel.
59 FCExpress Upload This point is activated while Express is reading a configuration from the
panel.
60 Inhibit No Response
faults
During commissioning, the system can be set not to report no response
faults for devices missing at restart. Devices that do reply, then stop
replying are still reported. This point is linked to commissioning state and
records an entry in the panel log.
61 Config File Fail This point is activated while a download from Express is active on the
panel.
62 Stage 1 Image Fail The regular checking of the stage 1 boot loader failed.
63 Stage 2 Image Fail The regular checking of the stage 2 boot loader failed.
64 App. Image Fail The regular checking of the main panel firmware failed.
65 X501 Service Mode This point is activated if the Service mode link on the CPU801 is fitted at
panel restart.
Point
Address
Label Use
Table 1: FIM Local I/O Pseudo Points (cont.)