FireClass Panels and Repeaters Alarm operator actions
User Manual Doc. version 2.0 13
The panel resumes normal operation, see Fig.3. There
are no lit fault LEDs.
2.8.5 Clear a system fault on repeater
The following procedure details how to clear the system fault on a MT2 FireClass FC600 repeater.
1 Open the repeater door.
2 Press the Reset button inside the repeater on the CUI board, near the keyswitch shown in Fig.6.
3 Pressing the Reset button restarts the repeater and clears the system fault LED on the repeater.
4 Then, press the green RESET key on the panel connected to the repeater to clear the fault on the panel.
Fig. 5: FC-FI
1 – SW1 MASTER RST button