32 User Manual Doc. version 2.0
4.9 Test Buzzer, LEDs & Display FireClass Panels and Repeaters
Navigate to a point address and press Enter.
The screen displays the point Description, Device Type
and Use, the Loop address and the Zone number.
For multi-channel devices, you can modify either only
the label and description or both, and zone of the chan-
nels. You cannot change any device to a multi-channel
one.
Synchronize Network
After you have performed the respective operations
such as changed text, inserted, deleted or modified the
points, use the Configuration menu, Restart option.
Before the panel is restarted on a networked system, to
include changes updated for the front panel configura-
tion, the following message appears:
After restart do a Fire Reset to synchro-
nize the network.
It serves as a reminder for the user to perform a fire
reset to synchronize the changes.
Note that this message does not appear if the panel is
restarted for a non-networked system.
4.8.5 Auto Config.
Use the 7 – Auto Config. option on the Configuration
screen to enable auto configuration. Using auto config-
uration, the panel can learn what devices are connected
on the loops and what multi-point devices, such as the
sounders with beacons, or the multi-point ancillary
devices, are connected on the loops.
On the Auto Config. screen, specify the Loop, Topol-
ogy, and Zone and press Enter.
The Auto Config. screen shows the Panel, Loop,
Topology, and Zone. The Zone
text displayed below the
Zone number refers to:
The number of devices, the detector can see from
the left- side of the loop.
The number of devices, the detector can see from
the right-side of the loop.
The number of devices that are visible to the detec-
tor from both the right and left sides of the loop.
The number of devices that are already present in
the configuration.
To overwrite the loop details present in the configura-
tion file with data derived from actual devices on the
loop, choose “Yes-overwrite all” and press Enter to
accept the option.
Choose ‘Abort’ to discard the process of overwriting the
loop configuration file.
Choose ‘Yes’ or ‘No’ for the overwriting to take effect or
not.
If you would like to add new devices to the already exist-
ing devices in the configuration, choose ‘No - Only add
new’ and press Enter to accept the option.
4.9 Test Buzzer, LEDs & Display
Use the 9 – Test Buzzer, LEDs & Display on the Main
Menu to momentarily activate the internal buzzer, all
the pixels of the LCD, and all the LEDs.
If any of these do not happen there is a fault.
CAUTION
This option should be used with care. You can
overwrite and lose the current panel
configuration.
Number of devices
The number of devices that are visible to the
detector should be equal from both the left
and right-sides of the loop, or else there is a
break in the loop wiring.