20 User Manual Doc. version 2.0
4 Doc. version 2.0Menu details FireClass Panels and Repeaters
4 Doc. version 2.0Menu details
The sections below detail the menu options. Access the
menu options with the alphanumeric keypad.
For further information on accessing the Main Menu
and viewing different menu options, see section 3.1.1
“Logging on” on page 17.
4.1 Accept Events
Use the 1– Accept Events option on the Main Menu
to review and then accept an event. Use the Accept
(F3) key to acknowledge that you have read the event
and are aware of it.
Note: The 1 – Accept Events option is not available for
all users or in all countries.
4.2 View Status
Use the 2 – View Status option on the Main Menu to
view the details and status of items in the system. The
status might be Normal or Fault, for example.
4.2.1 Full Point
Use the 1 – Full Point option on the View Status
screen to see complete details and status information
of the Full Point.
Full points include real (physical) points that relate to
diagnostic status.
Select the option for the type of point, as appropriate.
The types of point are as follows:
Loop Point: Points on the addressable loop.
RBus Point: Points on the Remote Bus, such as I/O
expansion boards.
Local I/O Point: Local points that are not on the
Remote Bus or addressable loop.
Lnet Point: Local network points.
Loop Point
For the Loop Point option, specify a point address to see
the point information and status. The screen shows the
point information and status. The information includes
the point’s zone number, description, the sector
description (if applicable), the device description, and
the loop ID. For input devices, the Output column is not
applicable and will always be blank. Similarly, for output
devices the Input column will be blank.
The status for input devices can be one of the following:
Normal
Fault
Active
Pre-Alarm
The status for output devices can be one of the follow-
ing:
On
Off
Pulse 1
Pulse 2
RBus Point
After selecting the RBus option from the Full Point
screen, you can specify the appropriate Point and RBus
numbers. Select the Category option according to what
you want to investigate at your specified numbers. The
Category options are:
Real: Physical items (as opposed to logical items),
that are directly connected at the RBus point.
XBus: Further expansion hardware.
Local I/O Points
After selecting the Local I/O option from the Full Point
screen, you see the same type of screen as after select-
ing the RBus option but without the RBus item.
For Category, the same options are available, but with
the addition of these options:
Timer: Timed events such as switching events
between Day and Night modes.
Menu: Additional menu items that may have been
configured into the panel. These can be enabled or
disabled.
Lnet Point
After selecting the Lnet Point option from the Full Point
screen, specify the appropriate Point and LNET num-
bers. Select the Category option according to what you
want to investigate at your specified numbers. Select
from either:
Real: Physical items (as opposed to logical items),
that are directly connected at the RBus point.
XBus: Further expansion hardware.
4.2.2 Point I/P only
Use the 2 – Point I/P only option on the View Status
screen to review input points on the loop only, such as
call points and detectors.
If you specify an output point address, it will be indi-
cated as invalid.