COMMISSIONING
Only an authorized field acceptance provider shall proceed with Diesel Fire Pump
controller commissioning. If you do not have the required training and author-
ization, contact factory.
Untilcommissioningiscompleted,thecontrollermainscreenisreplacedbythecommissioning
menuandtheautomaticmodeisdisabled.
Procedure
Tocommissionthecontroller:
1.
SecurethedoorinclosedpositionthenputthecircuitbreakerdisconnectingmeansinON
position.
2.
Loginwithyourpasswordandcompletethefirststartupmenuonthescreen.
3.
Onceallthenecessarystepsarecompletedandthatyouareloggedinwithyourpassword,
the"ServiceDone"buttonwillbecomeonline.
4.
Pressthe"ServiceDone"buttononceyouaresatisfiedwiththereadingsandparameters.
5.
Downloadthelogstosaveinyourreport.