V2024.02 8
persons.Thisdevicemustnotbeco-locatedoroperatinginconjunctionwithanyotherantennaor
transmitter.
Thisdevicecontainslicence-exempttransmitter(s)/receiver(s)thatcomplywithInnovation,
ScienceandEconomicDevelopmentCanada’slicence-exemptRSS(s).Operationissubjectto
thefollowingtwoconditions:
1.
Thisdevicemaynotcauseinterference.
2.
Thisdevicemustacceptanyinterference,includinginterferencethatmaycauseundesired
operationofthedevice.
Compliance:CANICES-003(B)/NMB-003(B)
Thisdevicecomplieswithpart15oftheFCCRules.Operationissubjecttothefollowingtwocon-
ditions:(1)Thisdevicemaynotcauseharmfulinterference,and(2)thisdevicemustacceptany
interferencereceived,includinginterferencethatmaycauseundesiredoperation.
Note:ThisequipmenthasbeentestedandfoundtocomplywiththelimitsforaClassAdigital
device,pursuanttopart15oftheFCCRules.Theselimitsaredesignedtoprovidereasonablepro-
tectionagainstharmfulinterferencewhentheequipmentisoperatedinacommercialenvir-
onment.Thisequipmentgenerates,uses,andcanradiateradiofrequencyenergyand,ifnot
installedandusedinaccordancewiththeinstructionmanual,maycauseharmfulinterferenceto
radiocommunications.Operationofthisequipmentinaresidentialareaislikelytocauseharmful
interferenceinwhichcasetheuserwillberequiredtocorrecttheinterferenceathisownexpense.
“Changesormodificationsnotexpresslyapprovedbythepartyresponsibleforcompliancecould
voidtheuser'sauthoritytooperatetheequipment.”
Location
Consult the appropriate job plans to determine the controller mounting location.
Thecontrollershallbelocatedascloseaspracticaltotheengineormotoritcontrolsandshallbe
withinsightoftheengineormotor.Thecontrollershallbelocatedorprotectedsuchthatitwillnot
bedamagedbywaterescapingfrompumporpumpconnections.Currentcarryingpartsofthe
controllershallbenotlessthan12in.(305mm)abovethefloorlevel.
WorkingclearancesaroundcontrollershallcomplywithNFPA70,NationalElectricalCode,
Article110orC22.1,CanadianElectricalCode,Article26.302oranyapplicablelocalcodes.
ThestandardcontrollerenclosureisratedNEMAType2.Itistheinstaller’sresponsibilitytoinsure
thateitherthestandardenclosuremeetstheambientconditionsorthatanenclosurewithan
appropriateratinghasbeenprovided.Controllersmustbeinstalledinsideabuildingandtheyare
notdesignedforoutsideenvironment.Thepaintcolormaychangeifthecontrollerisexposedto
ultravioletraysforalongperiodoftime.
Mounting
TheDieselFirePumpcontrollershallbemountedinasubstantialmanneronasingleincom-
bustiblesupportingstructure.