MAINTENANCE
Firetrolcontrollersarecoveredbyalimitedwarrantyandbackedbya10-yearsservicelifeoruntil
supplylast,providedthatproperinstallation,commissioning,useandmaintenanceofthecon-
trollerismadeasperthisdocument,NFPA25,andanymaintenancestandardapplicable.
Propercontrollerperformancemustbeassertedatleastonceaweekbyexecutingthefollowing:
1.
Withthesystembeingatnominalpressure,ensurethatthepressurereadingiswithintol-
erances
2.
Performateststartsequenceandverifythat
1.
Theenginestartsnormally,notablywithrespecttocrankcyclesandtime
2.
Therearenoalarms
3.
Thepumpisabletorisethepressureabovethecut-out
4.
Theenginestopswhenthepressureisabovecut-outaftertheconfiguredtestdur-
ationtime
Inadditiontotheabove,thefollowingpreventativemaintenancemustbeperformedatleastonce
year:
1.
Turnoffthecontroller
2.
Doavisualinspectionoftheexteriorofthecontroller
3.
Opentheenclosureanddoavisualinspectionoftheinteriorofthecontroller
4.
Makesurethatthereisnodustaccumulationinsidethecontroller
5.
Inspectthetightnessofeachdeadcable
6.
Putthecontrollerbackinservice