EasyManua.ls Logo

Fireye YB110 - YP100 Operating Sequence; YP100 Terminal Sequence Chart

Fireye YB110
56 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
28
£
YP100 OPERATING SEQUENCE
Terminal
PTFI MTFI AUTO Post
Purge
STANDBY
3
Operating control
M
Cycle complete
Air flow (terminal P) must close within 10 seconds of HFS (M-8) closing
P
Valve closes in one second
13 (POC)
Proof of valve closure
Don't care state
X (HI)
Purge Complete
12 (LO)
11 (Auto)
PTFI/MTFI times keypad selectable
6 (PV)
15 s
10 s
5 (IGN/PV)
10 s
W (IGN)
5s
7 (MV)
Programmable time begins (30 sec minimum)
8 (HFS)
LFS must be closed Don't care state
D (LFS)
30 s LFS

Related product manuals