FIRST STOP SAFETY 20
MemoryPAT-Blu Issue 1.2
As soon as the appliance is switched ON the MemoryPAT-Blu will continue with
the test. Note that not all appliances have an ON switch and it may not be
possible to switch some appliances ON. In this case the user can skip this check
and carry on with the main testing by pressing the Class II button again. If the
user does neither then the unit should abort this test and power down.
The test will now run and the display will show the test results for the Insulation
Resistance as well as an overall Pass or Fail.
Once the testing is complete, record the results and the unique test number in
the Test Record.
Note: On Class II appliances, such as a hair dryer where there is no exposed
metal, the test lead can be left unconnected.
TESTING IEC LEADS
When testing IT equipment with detachable IEC leads, it is important to test
these as individual items. Plug both ends of the IEC lead into the MemoryPAT-
Blu. One end into the mains socket and the other end into the IEC socket.