EasyManua.ls Logo

Fisher DPR900 - Page 28

Fisher DPR900
140 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Jumper 9 is used to terminate the last controller on the RS-485
communication link. When the link is used, this jumper must be cut on
all but the last controller on the link. Otherwise, it should remain intact.
2.6
Low-Level Temperature Input
A DPRlOO Series Temperature Input Module may be plugged into the
controller to allow direct connection of a low-level input signal. The
controller internally connects this input to All. This disables All for
other uses. For further information on the DPRlOO, refer to Fisher
Controls Bulletin 6.1 :DPRlOO. The figure illustrates the wiring of the
temperature input module.
Signal Ground
Notes:
D When a temperature input nwdule is connected to All,
jumper 1 must be cut, and Jumper 5 must be intact. A
floating ground (zero) is n
md. DPR90M06
FCODE 119
must
be set to Option 2 (O-20 mA,
O-5 V) if a DPRlOO Series Temperature Input
Module is used.
UM6.l:DPR900:9102