5-6
Configuration
(FISHER”)
Function FGODE Option No Default Selected
klU? Value
All Signal 119 4-20mA. I-5V 1 1
Range O-20mA. 0-5V 2
Do not use FCODE 118, unless a DPRIOO
Temperature Input Module is being used. Also,
ensure that the appropriate temperature range is
used (OC or OF).
Function
Temperature
Input All
-CODE Option NO
118 Disabled 0
100 ohm Platinum RTD. “C 1
Type J Thermocouple, ;C
2
Type K Thermocouple, OC 3
Type R Thermocouple, OC
Type S Thermocouple ,OC
100 ohm Platinum RTD, OF 6
Type J Thermocouple, OF 7
Type K Thermocouple, OF 8
Type R Thermocouple, OF 9
Type S Themwcouple. OF 10
Ensure that the square-root extraction function
(FCODE 107) is set to 0 (disabled), if a
temperature input module is connected to the
controller.
When using the PV monitoring function, the
second temperature transmitter (connected to Al3)
must have the same measuring range and
engineering unit (EU) values as the transmitter or
sensor connected to All.
lefault
JkllW
0
lJM6.1:DPR900:9102
May 1991