5-30 Configuration
(PISHER”)
5.7.5
0
R
FCODE 142
Blocking
Remote/Local Setpoint Switching
Put the controller in remote mode, enabling the configured remote
setpoint options, by pressing the R button. This enables either an
external remote setpoint or the extra internal setpoint. The user
chooses the setpoint to be enabled via FCODE 142.
Al2
RSP
0
R
_ FCODE 142
,-
SP
FCODE 12 _
ESP
Function FCODE
Option No Default
Selected
ValW? VLlSW
Automatic
142 Disabled
1 1
Setpoint
Switches to remote setpoint
2
Switching
Switches to extra internal setpoint 3
A discrete input signal connected to Dll or Dl2, and configured using
FCODE 111, may switch the controller from the remote setpoint to the
extra internal setpoint value in the following situation:
fl The controller is in the remote mode.
H The connected and configured discrete input signal becomes
active.
In this situation the R button remains lit to indicate that manual control
is not possible. DO2 is active when the R button is lit as an external
indicator of the controller mode.