FCODE
114
Option
No Default Selected
V&It? V&K?
Disabled 0
0
Process value 1
Active setpoint 2
Local setpoint 3
Calculated Remote setpoint 4
Internal output signal 5
Q
&
Note
The controller self-test generates an error (E103) if
FCODE 114 is other than 0 and A02 terminals (11
and 12) are open.
Set FCODE 124 to select the A02 output signal range.
Function FCODE
Option
No Default Selected
Value Value
I
1
I
I
I I
Signal
124 G20mA 1
Range &20mA 2 2
A02
Q
4
Note
If the controller is using a remote setpoint value
and FCODE 140 is configured for Option 1 (the
extra internal setpoint value does not track the
remote setpoint value), then the extra internal
setpoint may be sent out on A02 by selecting
FCODE 114, Option 2.
Q
4
Note
The A01 output signal represents the actual
bargraph value (O-100%). If setpoint value
limiting (FCODE 106) is enabled, the output signal
is resealed to represent 0-i 00% of the limited
output or SP span, not necessarily the full SP or
PV potential.
Change 1 -September 1991