Variable Name
52 SPOOL_END_LIMIT XDTB_MD FLOAT 297 U_INT NO SS_highLimit NRW Spool End Limit
53 SPOOL_PERCENT XDTB_MD FLOAT 298 U_INT /100 SS_pctYellow R Spool Percent Yellow
16 VALVE_TRAVEL_
DISTANCE
XDTB_MD FLOAT 301 U_LONG /100 ValveTravel
Distance
R Valve Travel Distance
17 VALVE_TRAVEL_HIGH_
START
XDTB_MD FLOAT 302 U_LONG /100 ValveTravelHigh
Start
RW Valve Travel High Start
18 VALVE_TRAVEL_HIGH_
END
XDTB_MD FLOAT 303 U_LONG /100 ValveTravelHigh
End
RW Valve Travel High End
19 VALVE_TRAVEL_
PERCENT_YELLOW
XDTB_MD FLOAT 304 U_INT /100 ValveTravel
PercentYellow
NR Valve Travel Percent Yellow
20 VALVE_CYCLE_COUNT XDTB_MD USNIGNED 32 305 U_LONG NO ValveCycle
Count
R Valve Cycle Count
21 VALVE_CYCLE_HIGH_
START
XDTB_MD UNSIGNED 32 306 U_LONG NO ValveCycleHigh
Start
RW Valve Cycle High Start
22 VALVE_CYCLE_HIGH_
END
XDTB_MD UNSIGNED 32 307 U_LONG NO ValveCycleHigh
End
RW Valve Cycle High End
23 VALVE_CYCLE_
PERCENT_YELLOW
XDTB_MD FLOAT 308 U_INT /100 ValveCycle
PercentYellow
NR Valve Cycle Percent Yellow
40 SPOOL_TRAVEL_
PERCENT
XDTB_MD FLOAT 311 U_LONG /100 SpoolTravel R Spool Travel in Percent
38 SPOOL_TRAVEL_HIGH_
START_LIMIT
XDTB_MD FLOAT 312 U_LONG /100 ST_HighStart
Limit
RW Spool Travel High Start Limit
39 SPOOL_TRAVEL_HIGH_
END_lIMIT
XDTB_MD FLOAT 313 U_LONG /100 ST_HighEnd
Limit
RW Spool Travel High End Limit
41 SPOOL_TRAVEL_
PERCENT_YELLOW
XDTB_MD FLOAT 314 U_INT /100 ST_pctYellow NR Spool Travel Percent Yellow
35 SPOOL_CYCLES XDTB_MD UNSIGNED 32 315 U_LONG NO SpoolCycles NR Spool Cycles
33 SPOOL_CYCLE_HIGH_
START_LIMIT
XDTB_MD UNSIGNED 32 216 U_LONG NO SC_HighStart
Limit
RW Spool Cycle High Start Limit
34 SPOOL_CYCLE_HIGH_
END_LIMIT
XDTB_MD UNSIGNED 32 317 U_LONG NO SC_HighEnd
Limit
RW Spool Cycle High End Limit
37 SPOOL_CYCLE_
PERCENT_YELLO
XDTB_MD FLOAT 318 U_INT /100 SC_pct_Yellow NR Spool Cycle Percent Yellow
36 CYCLE_TRAVEL_RESET XDTB_MD BIT_STRING 319 U_CHAR NO SpoolCycle
TravelReset
RW Reset Bits to reset the Spool
Cycle and the Spool Travel
Parameters
42 TREND_STATE XDTB_MD UNSIGNED 8 321 U_CHAR NO TrendLock RW Trending State
43 TREND_INDEX XDTB_MD UNSIGNED 8 322 U_CHAR NO TTIndex RW Index into the Trending Data
Array
44 TREND_DATE XDTB_MD UNSIGNED 8 323 U_CHAR NO DateTimeStamp R Reserved for Future Use
83-91 TREND_DATA_n XDTB_MD ARRAY 324 ARRAY NO TrendData R Trending Data Array
58 FORCE_OF_PRESSURE XDTB_MD INTEGER 16 331 S_INT NO Fp R Force of Pressure
59 FORCE_SPRING XDTB_MD INTEGER 16 332 S_INT NO Fs R Spring Force
60 FORCE_ACTUATOR XDTB_MD INTEGER 16 334 S_INT NO Fa R Actuator Force