What to do if Flowserve Logix 520MD+ are stuck fully open or closed?
- SSusan EllisAug 15, 2025
If your Flowserve Valve Positioner's position is fully open or closed and doesn't respond to commands, here's what to check: 1. Perform stroke calibration (Quick-Cal). 2. Verify hardware connections of the inner-loop hall sensor. 3. Check ATO (Air-to-open) and ATC (Air-to-Close) settings and recalibrate using Quick-Cal to apply settings. 4. Verify ATO/ATC actuator tubing. 5. Consider replacing the electro-pneumatic converter. 6. Adjust the inner-loop offset to see if proper control resumes. Possible causes are uncalibrated stroke, disconnected inner-loop hall sensor, wrong air action entered in software, backward actuator tubing, malfunctioning electro-pneumatic converter, or incorrect inner-loop offset.