4 SPECIFICATIONS
Table 1: Input Signal
Input Signal Range 4 - 20 mA (HART)
Compliance Voltage 10 VDC
Voltage Supply (maximum) 30 VDC
Minimum Required Operating
Current
3,6 mA without AO
3,83 mA with AO
Table 2: Stroke Output
Feedback Shaft Rotation Min. 15°, max 90°
40° recommended for linear
applications
Table 3: Air Supply
Air Supply Quality Free from moisture, oil and dust
per IEC 770 and ISA-7.0.01
Input Pressure Range 1,5 to 6,0 bar (22 to 87 psi)
Air Consumption (steady state)
0,08 Nm³/h @ 1,5 bar
(0,047 SCFM @ 22 psi)
0,12 Nm³/h @ 6,0 bar
(0,071 SCFM @ 87 psi)
Table 4: Output Signal
Output Pressure Range 0 to 100% of air supply pressure
Output Flow Capacity 2,4 Nm³/h @ 1,5 bar
(1,41 SCFM @ 22 psi)
7,0 Nm³/h @ 6,0 bar
(4,12 SCFM @ 87 psi)
Table 5: Shipping Weights
Base Positioner without
Accessories
1,2 kg (2,65 lbs)
Table 7: Environmental Conditions
Operating Temperature -40 °C to +80 °C
(-40 °F to +178 °F)
Transport and Storage
Temperature
-40 °C to +80 °C
(-40 °F to +178 °F)
Operating Humidity 0 to 100% non-condensing
Table 6: Performance Characteristics (typical)
Linearity < +/- 1,0%
Resolution < 0,1%
Repeatability < 0,2%
Deadband < 0,2%
Table 9: Limit Switches (optional)
Type P&F SJ2-S1N
Load current < 1 mA < 3 mA
Voltage range 5 - 25 VDC
Hysteresis 0,2 %
Temperature -25
°C to
100
°C (
-13
°F to
212
°F)
Type P&F SJ2-SN
Load current < 1 mA < 3 mA
Voltage range 5 - 25 VDC
Hysteresis 0,2 %
Temperature -40
°C to
100
°C (
-40
°F to
212
°F)
Type P&F SJ2-N
Load current < 1 mA < 3 mA
Voltage range 5 - 25 VDC
Hysteresis 0,2 %
Temperature -25
°C to
100
°C (
-13
°F to
212
°F)
3 LOGIX 520MD OVERVIEW
The Logix 520MD is a two-wire, 4-20 mA input digital valve
positioner with HART communication. The Logix 520MD
positioner controls single-acting actuators with linear
and rotary mountings. The Logix 520MD is completely
powered by the 4-20 mA input signal. The minimum input
signal required to function is 3,6 mA.
Since the positioner is insensitive to supply pressure
changes and can handle supply pressures from 1,5 to 6 barg
(22 to 87 psig), a supply regulator is usually not required;
however, in applications where the supply pressure is
higher than the maximum actuator pressure rating a supply
regulator is required to lower the pressure to the actuator’s
maximum rating (not to be confused with operating range).
A coalescing air filter is recommended for all applications
Table 8: Hazardous Area Specifications
ATEX II 1 G Ex ia IIC T5 - T6
II 3 G Ex ic IIC T5 - T6
FM
Class I, Division 2, Groups A,B,C,D Temp. Class. T4 Ta = 85°C
Class I Zone = Group IIC T4 Ta = 85°C
Class I, Division 2, Groups A,B,C,D Temp. Class. T4 Ta = 85°C
CSA Class I Division 1, Groups A,B,C,D
Class I Division 2, Groups A,B,C,D

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Flowserve Logix 520MD Series and is the answer not in the manual?

Flowserve Logix 520MD Series Specifications

General IconGeneral
BrandFlowserve
ModelLogix 520MD Series
CategoryValve Positioners
LanguageEnglish

Related product manuals