F116-P
DIFFERENTIAL / SUM FLOW COMPUTER
with analog and pulse outputs
Signal input flowmeter: pulse, Namur and coil
Signal outputs: (0)4-20mA / 0-10V ref. flow rate and pulse ref. total and
negative flow
Options: Intrinsically safe, Modbus communication and backlight
F-Series - Field mounted indicators for safe and hazardous areas.
More info: www.fluidwell.com/fseries

Table of Contents

Question and Answer IconNeed help?

Do you have a question about the Fluidwell F116-P and is the answer not in the manual?

Overview

Fluidwell F116-P Differential / Sum Flow Computer

The Fluidwell F116-P is a microprocessor-driven instrument designed to measure, display, and calculate flow rates and totals from two flow meter inputs. It can determine differential or summed flow rates and totals, making it suitable for a wide range of industrial applications.

Function Description

The F116-P processes signals from two flow meters, providing real-time flow rate and totalized quantity information. Its core functions include:

  • Flow Measurement: Calculates and displays the flow rate and total from two independent flow meter inputs.
  • Differential/Sum Calculation: Determines either the difference or the sum of the two flow meter inputs for both flow rate and total.
  • Signal Input Versatility: Compatible with various flow meter signal types, including passive or active pulse, Namur, and sine wave (coil) signals.
  • Standard Outputs:
    • Pulse Output (R1): Transmits a pulse representing a totalized quantity, programmable according to user requirements.
    • Negative Flow Output (R2): Provides a pulse output specifically for negative flow.
    • Analog Output: Offers a linear (0)4-20mA or 0-10V signal to represent the actual flow rate. The signal limits are tunable.
  • Optional Features:
    • Intrinsically Safe (Type XI): Available for use in hazardous areas, adhering to ATEX and IECEx certifications.
    • Modbus Communication: Supports RS232/RS485/TTL for data exchange, with battery-powered options.
    • Backlight: Enhances display readability in various lighting conditions.
    • Mechanical Relay or Active Output: Provides additional output flexibility.
    • Power and Sensor Supply Options: Offers various configurations for powering the unit and connected sensors.
    • Enclosure Types: Available in panel mount, wall mount, and weather-proof enclosures, including flame-proof options.

Important Technical Specifications

Display:

  • High-intensity numeric and alphanumeric LCD, UV-resistant.
  • Seven 17mm (0.67") and eleven 8mm (0.31") digits.
  • Various symbols and measuring units.
  • User-definable refresh rate: 8 times/sec to 30 secs.
  • Optional LED backlight (Type ZB) for improved readability in full sunlight and darkness, requiring external power (PX, PD, PF, PM types).

Enclosures:

  • General: Die-cast aluminum or GRP (Glass fiber Reinforced Polyamide) with polycarbonate window, silicone and EPDM gaskets. UV stabilized and flame retardant material.
  • Control Keys: Three industrial micro-switch keys with UV-resistant silicone keypad.
  • Coating (Aluminum only): UV-resistant 2-component industrial coating.
  • Panel Mount:
    • Dimensions: 130 x 120 x 60mm (5.10" x 4.72" x 2.38") WxHxD.
    • Panel cut-out: 115 x 98mm (4.53" x 3.86") WxH.
    • Protruding at front: 31mm (1.22").
    • Classification: IP65 / TYPE 4X.
    • Weight (approx.): GRP 450 gr (1.0 lbs), Aluminum 0.6 kg (1.3 lbs), Stainless steel 1 kg (2.2 lbs).
  • Field/Wall-Mount:
    • Dimensions: 130 x 120 x 75mm (5.10" x 4.72" x 2.95") WxHxD.
    • With extended back: 130 x 120 x 90mm (5.10" x 4.72" x 3.54") WxHxD.
    • Classification: IP67 / TYPE 4X.
    • Weight (approx.): GRP 0.6 kg (1.3 lbs), Aluminum 1 kg (2.2 lbs), Stainless steel 1.5 kg (3.3 lbs).

Operating Temperature:

  • Operational: -40°C to +80°C (-40°F to +176°F).
  • Intrinsically Safe: -40°C to +70°C (-40°F to +158°F). For EPL Da: -40°C to +50°C (-40°F to +122°F).
  • Relative humidity: 90%, no condensation allowed.

Power Supply:

  • Type AP (Loop-powered): 4-20mA output signal, 8-30V DC. Max. 0.5 Watt.
  • Type PB (Standard Lithium Battery): Life-time up to 5 years (SAFE AREA ONLY).
  • Type PC (Intrinsically Safe Lithium Battery): Life-time up to 5 years.
  • Type PD: 8-24V AC / 8-30V DC. Max. 5 Watt.
  • Type PD-ZB: 10-24V AC / 12-30V DC. Max. 5 Watt.
  • Type PD-XI: 16-30V DC. Max. 1 Watt.
  • Type PF: 15-24V AC / 20-30V DC. Max. 15 Watt.
  • Type PM: 115-230V AC. Max. 15 Watt.
  • Type PX: 8-30V DC. Max. 0.75 Watt.
  • Type PX-ZB: 12-30V DC. Max. 1.5 Watt.
  • Type PX-XI: 8-30V DC. Max. 0.75 Watt.

Sensor Supply:

  • Internal: 3V (low power signal), 1.2V DC (coil pick-up). Max 0.1mA.
  • External: 8.2V, 12V, 24V options, with varying max currents (20mA to 400mA depending on type).

Flowmeter Inputs (Type P):

  • Signal types: NPN, NPN-LP, Reed, Reed-LP, PNP, PNP-LP, Namur, Coil-HI, Coil-LO, 8-1 DC, 12 DC, 24 DC.
  • Frequency: Minimum 0 Hz - maximum 7 kHz for total and flow rate (depends on signal type and internal low-pass filter).
  • K-Factor: 0.000010 - 9999999 with variable decimal position.

Analog Output:

  • Function: Transmitting differential or summed flow rate.
  • Accuracy: 10 bit, Error < 0.05%, update 10 times a second.
  • Load: max. 1 kOhm.
  • Types: Active 4-20mA, Active 0-20mA, Passive floating 4-20mA (Intrinsically safe only), Passive galvanic isolated, Passive 4-20mA (output loop powered), Active 0-10V.

Pulse Outputs:

  • Two pulse outputs, transmitting (differential or summed) quantity, and/or increase or decrease of total.
  • Max. frequency: 500 Hz. Pulse length user definable between 0.001 up to 9.999 seconds.
  • Types: Active 24V DC transistor (max. 50mA), Isolated mechanic relay (max. 230V AC - 0.5A), Passive transistor (max. 50V DC - 300mA).

Communication (option):

  • Protocol: Modbus (RTU, ASCII).
  • Speed: 1200, 2400, 4800, 9600.
  • Addressing: 1-255.
  • Types: RS232 (Type CB), RS485 2-wire (Type CH), RS485 4-wire (Type CI), TTL (Intrinsically safe only, Type CT).

Data Protection:

  • EEPROM backup of all settings, running totals every minute.
  • Data retention at least 10 years.
  • Configuration settings can be password protected.

Usage Features

The F116-P is designed for user-friendly operation with a clear LCD and intuitive control panel.

Operator Level Functions:

  • Main Display: Shows total on the upper line and flow rate on the bottom line. Arrows indicate flow rate trend.
  • Display Selection: The SELECT key allows toggling between total, accumulated total, flow rate A, accumulated total A, flow rate B, and accumulated total B.
  • Clear Total: The CLEAR key, pressed twice, resets the total value. Accumulated total cannot be reset.
  • Low-Battery Alarm: A "low-battery" icon indicates when the battery voltage drops, prompting replacement.
  • Alarm Indicator: Alerts the operator to errors or dangers, with details available in the problem-solving appendix.

Setup Level Functions (Configuration):

  • Access: Pressing the PROG-key for 7 seconds (and entering a password if set) grants access to the SETUP-level.
  • Navigation:
    • PROG-key: Used to start programming, save values, and scroll back through function groups.
    • SELECT-key: Selects the next function or item in a list, increments digits.
    • CLEAR-key: Selects the previous function or item, selects the next digit, or toggles the negative sign when combined with SELECT.
  • Programming Sequence: Allows users to program new values or settings, including K-Factors, engineering units, signal selection, and power management options.
  • Display Settings: Configurable display refresh rate (FAST, 1 sec, 3 sec, 15 sec, 30 sec, off) and backlight brightness (0% to 100%).
  • Measurement Methods: Four methods for handling positive or negative flow (Bi-directional, Not-negative, Threshold, Stationary) to prevent undesired display readings.
  • Analog Output Tuning: Precise tuning of the (0)4mA or 0V minimum signal and 20mA or 10V maximum signal.
  • Flowmeter Signal Selection: Allows selection of specific flowmeter signal types (NPN, Reed, PNP, Namur, Coil, Active Pulse) and low-pass filters for noise reduction.
  • Power Management: "Operational" mode for normal use, and "Shelf" mode for extended storage with minimal power consumption.

Maintenance Features

The F116-P is designed for reliability with minimal maintenance, but certain procedures are essential for optimal performance and safety.

General Directions:

  • Qualified Personnel: Mounting, electrical installation, start-up, and maintenance must be performed by trained and authorized personnel.
  • Safety Precautions: Always ensure leads are potential-free before opening the enclosure. Discharge static electricity before handling electronics.
  • EMC Compliance: Install in accordance with EMC guidelines.
  • Grounding: Properly ground the metal enclosure, especially if hazardous live voltage is present.
  • Intrinsically Safe Applications: Follow specific instructions in Chapter 5 for intrinsically safe installations.
  • Humidity Control: For low-temperature or high-humidity environments, dehumidify the internal atmosphere (e.g., using desiccant) to prevent condensation. Replace desiccant periodically.

Battery Life-Time:

  • Influenced by sensor type (NPN/PNP consume more than coil), input frequency (higher frequency shortens life), analog output signal (disable if not in use or use external power), display update rate (slow rate extends life), pulse output, communications, and low temperatures.
  • It is strongly advised to disable unused functions to extend battery life.

Periodic Checks:

  • Enclosure and Wiring: Inspect the condition of the enclosure, cable glands, front panel, and input/output wiring.
  • Process Accuracy: Re-calibrate the flowmeter and re-enter K-Factor alterations as needed due to wear and tear.
  • Low-Battery Indication: Monitor for the low-battery icon and replace the battery shortly after it appears.
  • Cleaning: Clean the window and enclosure with a lint-free cloth dampened with mild soap solution. Avoid aggressive solvents.

Repair Policy:

  • The product cannot be repaired by the user. Repairs must be carried out by the manufacturer or an authorized agent.
  • RMA Process: To initiate a repair, obtain a Return Material Authorization (RMA) from the supplier, complete a repair form with detailed problem information, and send the product to the provided address within 30 days.
  • Warranty: Products within the warranty period will be repaired or exchanged within three weeks. For out-of-warranty products, a repair estimate will be provided.

Battery Replacement Instructions:

  • Safety First: Before replacement, ensure the new battery's marking matches the installation type (refer to paragraph 6.3.1). Disconnect all leads and ensure the unit is potential-free.
  • Intrinsically Safe Batteries (Type PC): Only use certified FW-LiBAT-021 batteries (re-ordering nr. SPC02) with the correct Ex marking. Never use safe area batteries in hazardous areas.
  • Safe Area Batteries (Type PB): Use StdLIBAT021 batteries (re-ordering nr. SPB02).
  • Procedure:
    1. Open the enclosure and remove cable-connectors.
    2. Remove the protective cover by unscrewing two screws and lifting it.
    3. Disconnect the old battery connector.
    4. Remove the old battery from the plastic cover (do not remove the battery clip). Store it in a plastic bag or insulate the connector to prevent short circuits.
    5. Install the new, undamaged battery into the clip, ensuring correct wire orientation.
    6. Connect the new battery to its counterpart.
    7. Replace the protective cover and secure it with screws (<1Nm).
    8. Verify the screen comes on, then return cable-connectors and close the enclosure.
    9. Initialize date and time if required.
  • Disposal: Dispose of batteries according to international, manufacturer's, and plant owner's standards and regulations. Do not dispose of as general waste or incinerate; return to a recycling point.