E119-P
TOTALIZER WITH RECEIPT PRINTER DRIVER
and linearization, analog and pulse outputs
Signal input: Flowmeter - type P: Pulse, NAMUR and coil
Signal outputs: Analog referenced linearized flowrate
Scaled or unscaled pulse referenced total
Remote control: External reset with clear-lock
External end delivery with lock function
External print totalizer ticket
External reprint last ticket
E-Series - Explosion proof indicators for hazardous areas
More info: www.fluidwell.com/eseries

Table of Contents

Questions and Answers

  • W
    william45Aug 18, 2025
    Why is my Fluidwell E119-P Measuring Instruments flowmeter generating too many pulses?
    • L
      Luis HouseAug 18, 2025
      If your Fluidwell Measuring Instruments flowmeter generates too many pulses, check the settings for Total and Flowrate and the type of signal selected versus the actual signal generated. Also, verify the sensitivity of the coil input. Ensure proper grounding by reconnecting ground cables and avoiding ground loops, connecting the screen to the ground input terminal of the flowmeter input. Use screened wire for flowmeter signals.
  • W
    wendy59Aug 20, 2025
    What to do if the analog output of Fluidwell E119-P Measuring Instruments does not function properly?
    • Y
      ylaneAug 20, 2025
      If the analog output of your Fluidwell Measuring Instruments does not function properly, check the function mode and the settings for minimum and maximum flowrate. Also, verify the tuning of the minimum and maximum output current. Finally, confirm the connection of the external power supply.
  • D
    Danielle SmithAug 23, 2025
    How to troubleshoot a Fluidwell E119-P Measuring Instruments flowmeter that does not generate pulses?
    • L
      laura36Aug 23, 2025
      If your Fluidwell Measuring Instruments flowmeter does not generate pulses, check the signal selection in the SETUP menu. Verify the pulse amplitude and inspect the flowmeter, wiring, and connection of terminal connectors. Also, check the power supply of the flowmeter.
  • D
    David BlanchardAug 26, 2025
    What to do if the pulse output on my Fluidwell Measuring Instruments is not working?
    • E
      elizabethlopezAug 26, 2025
      If the pulse output of your Fluidwell Measuring Instruments does not function, check the function mode. Verify the pulse per quantity and ensure pulse width compatibility with the external device.
  • N
    nwilsonAug 28, 2025
    Why does my Fluidwell Measuring Instruments flowrate display zero when there is flow?
    • M
      markwilcoxAug 28, 2025
      If the flowrate displays "0 / zero" while there is flow (total is counting) on your Fluidwell Measuring Instruments, check the K-factor and time unit. Also, verify the flowrate calculation setting versus the flowrate cut-off. For example, if the cut-off is set to 10.0 seconds, the unit has at least 10 seconds to measure the number of pulses according to the calculation.
  • L
    Lori WatsonAug 30, 2025
    Why does the Fluidwell E119-P Measuring Instruments flowmeter display '0 / zero' when there is flow and the total is counting?
    • M
      Michael DanielsAug 30, 2025
      The flowrate might display zero while there is flow because of the K-factor and time unit settings. Check the FLOWRATE > TIME and FLOWRATE > K-FACTOR settings. Also, the flowrate calculation setting versus the flowrate cut-off could be the reason. For example, if the cut-off is set to 10.0 seconds, the unit needs at least 10 seconds to measure the number of pulses according to calculation. Verify the FLOWRATE > CALCULATION and FLOWRATE > CUT-OFF settings.
  • P
    pamela23Sep 2, 2025
    Why Fluidwell Measuring Instruments flowmeter generates too many pulses?
    • N
      Nicholas PhillipsSep 2, 2025
      The flowmeter might be generating too many pulses due to incorrect settings for Total and Flowrate. Check SETUP 5: FLOWMETER. It could also be due to the type of signal selected not matching the actual signal generated; again, verify this in SETUP 5: FLOWMETER. Another potential cause is the sensitivity of the coil input, which can also be adjusted in SETUP 5: FLOWMETER. Ensure correct grounding by reconnecting ground cables and avoiding ground loops, and connect the screen to the ground input terminal of the flowmeter input. Finally, ensure you are using screened wire for flowmeter signals.
  • B
    Brandon RobertsSep 4, 2025
    How to fix Fluidwell E119-P pulse output if it does not function?
    • A
      april23Sep 4, 2025
      If the pulse output isn't working, check the function mode in SETUP 8: RELAY OUTPUTS. Also, verify the pulse per quantity setting at 8.6: RELAY OUTPUTS > AMOUNT and ensure the pulse width is compatible with the external device by checking 8.5: RELAY OUTPUTS > WIDTH.
  • T
    Troy PhillipsSep 6, 2025
    How to troubleshoot Fluidwell E119-P flowmeter when it does not generate pulses?
    • S
      Sydney RodriguezSep 7, 2025
      If the flowmeter isn't generating pulses, first check the signal selection in SETUP menu using SETUP 5.1: FLOWMETER > SIGNAL [»25]. Then, verify the pulse amplitude as described in Section 6.4.10: Terminals S1-S3: Flowmeter input [»45]. Ensure the flowmeter, wiring, and terminal connectors are correctly installed according to Section 6.4: Electrical installation [»39]. Finally, confirm the power supply of the flowmeter is correctly set up, referring to Section 6.4.4: Voltage selection sensor supply [»41].
  • J
    James RiveraSep 9, 2025
    Why does the Fluidwell E119-P Measuring Instruments flowmeter generate too many pulses?
    • D
      Diamond ClarkSep 9, 2025
      The Fluidwell Measuring Instruments flowmeter might generate too many pulses due to several reasons: * Incorrect settings for Total and Flowrate. * A mismatch between the type of signal selected and the actual signal generated. * Incorrect sensitivity of the coil input. * Grounding issues: Reconnect ground cables and avoid ground loops. Connect the screen to the ground input terminal of the flowmeter input. * Incorrect wiring type: Use screened wire for flowmeter signals.