F110-P
FLOWRATE INDICATOR / TOTALIZER
Signal input flowmeter: pulse, Namur and coil.
Signal outputs: (0)4-20mA / 0-10V ref. flowrate and pulse ref. total.
Options: Intrinsically Safe, Modbus communication, external reset and
backlight.
F-Series - Field mounted indicators for safe and hazardous areas. More info: www.fluidwell.com/fseries
Question and Answer IconNeed help?

Do you have a question about the Fluidwell F110-P and is the answer not in the manual?

Fluidwell F110-P Specifications

General IconGeneral
BrandFluidwell
ModelF110-P
CategoryMeasuring Instruments
LanguageEnglish

Summary

Safety Instructions and Precautions

Life Support Application Disclaimer

The F110-P is not for life support; usage is at customer's risk.

Electrostatic Discharge Protection

Discharge yourself before handling electronics to prevent damage from static discharge.

Installation Compliance and Grounding

Unit must be installed per EMC guidelines and proper grounding for safety.

Intrinsically Safe Application Guidelines

Follow specific instructions for Intrinsically Safe applications for safe operation.

Disposal of Equipment

General Safety Rules and Measures

About the Operation Manual

Pictogram and Warning Guide

Explains warning, caution, and note pictograms for hazardous situations.

1. Introduction to the F110-P

System Description and Features

Overview of the F110-P flowrate/totalizer, its features, and capabilities.

Flowmeter Signal Input Types

Details on supported flowmeter signals like pulse, Namur, or sine wave.

Standard Output Signal Options

Description of scaled pulse output and analog output signals.

Unit Configuration and Display

Configuration of the Unit via SETUP-Level

SETUP-level configuration for K-factors, units, and signal selection.

Display Information and Options

Information on display features and available optional functionalities.

2. Operational Procedures

General Operational Guidelines

Operation by authorized personnel only; observe manual and safety rules.

Control Panel Key Functions

Explanation of the PROG/ENTER, SELECT, and CLEAR keys.

2.3. Operator Information and Functions

Flowrate and Total Display Management

Main display shows total and flowrate; options for flowrate-only view.

Procedure for Clearing Total Value

Procedure to re-initialize the total value using the CLEAR key.

Accumulated Total Display and Reset

SELECT key shows total and accumulated total; accumulated total is non-resettable.

Low-Battery Alarm Indication

Indicates low battery status and advises replacement with original batteries.

3. Configuration and Setup

Introduction to Configuration Chapters

Chapters for electricians/technicians covering software settings and hardware connections.

Programming Setup-Level Access

Configuration is done at SETUP-level, accessed by pressing PROG/ENTER for 7 seconds.

General Setup Access and Security

SETUP-level access, exit procedures, and pass code requirement.

Setup-Level Navigation and Structure

Matrix Structure of Setup Levels

Visual representation of the SETUP-level navigation structure.

Selecting Function Groups and Functions

SETUP is divided into groups and functions, navigated via keys.

Modifying Values in Setup

Changing or Selecting Values

Step-by-step guide for changing/selecting values in SETUP using the keys.

Returning to Operator-Level

Procedure to exit SETUP-level and return to normal operation.

3.2.2. Overview of Setup Functions

3.2.3. Explanation of Setup Functions: Total

Total Measurement Unit Settings

Defines measurement units for total and pulse output.

Total Decimal Place Settings

Sets the number of digits after the decimal point for total.

K-Factor Calculation for Total

Converts flowmeter pulses to quantity based on selected unit.

K-Factor Decimal Place Settings

Sets decimal places for K-factor, influencing accuracy.

Flowrate Settings Explanation

Flowrate Measurement Unit Settings

Sets measurement units for flowrate.

Flowrate Time Unit Settings

Defines time units (sec, min, hour, day) for flowrate calculation.

Flowrate Decimal Place Settings

Sets decimal places for flowrate display.

K-Factor Calculation for Flowrate

Converts flowmeter pulses to flowrate.

K-Factor Decimal Place Settings for Flowrate

Sets decimal places for K-factor.

Flowrate Calculation Pulses Setting

Determines pulses per measurement for flowrate calculation.

Flowrate Cut-Off Time Setting

Sets a minimum flow threshold to display zero.

Display and Power Management Configuration

Display Function Settings

Configures the large digits to display total or flowrate.

Power Management Features for Battery Life

Functions to extend battery life for battery-powered units.

LCD Update Rate Setting

Configures display refresh rate to manage power consumption.

Battery Mode Selection

Sets operational or shelf mode for battery-powered units.

5. Flowmeter Signal Selection

Signal Type Setup (SETUP 51)

Selects the flowmeter pickup/signal type from available options.

6. Analog Output Configuration

Analog Output EnableDisable Setting

Option to enable or disable the analog output signal.

Minimum Flowrate for Analog Output

Sets flowrate for minimum analog signal (0/4mA or 0V).

Maximum Flowrate for Analog Output

Sets flowrate for maximum analog signal (20mA or 10V).

Low Flow Cut-Off Percentage

Ignores low flow rates as a percentage of the full range.

Tuning Minimum Analog Output

Precisely tunes the minimum analog output value (0/4mA or 0V).

Tuning Maximum Analog Output

Precisely tunes the maximum analog output value (20mA or 10V).

Analog Output Filter and Relay Output

Analog Output Filter Setting

Stabilizes the analog output signal with a digital filter.

Pulse Output Period Time

Determines the pulse length for the transistor or relay output.

Pulse Per Quantity Setting

Sets the quantity per pulse generated for total.

8. Communication Options

Baud Rate Configuration

Sets communication speed for external control.

Bus Address Configuration

Assigns a unique address for communication purposes.

Communication Mode Selection

Selects communication protocol (Modbus ASCII or RTU).

9. Other Settings and Information

Model and Software Version Information

Information for support and maintenance about the unit's characteristics.

Serial Number and Pass Code

Information for support and maintenance; pass code protection.

Tag Number Configuration

Unique tag number for unit identification and communication.

4. Installation Guidelines

General Installation Directions

Instructions for mounting, electrical installation, and operation by trained personnel.

Installation and Surrounding Conditions

Guidance on installation location, IP classification, and environmental considerations.

4.3. Dimensions and Enclosures

Aluminum Enclosure Dimensions

Detailed dimensions for aluminum enclosures (HA to HZ types).

GRP Enclosure Dimensions

4.4. Hardware Installation Procedures

Introduction to Hardware Installation Safety

Safety precautions for hardware installation, including ESD and EMC.

Aluminum Enclosure Installation Requirements

Specific requirements for aluminum enclosures in potentially explosive atmospheres.

Grounding Aluminum Enclosures

Instructions for proper grounding of aluminum enclosures with PM power supply.

4.4.2. Sensor Supply Voltage Selection

Battery Powered Application Supply

Applications with limited supply voltage for signal output.

PDPFPM Sensor Supply Options

Sensor supply options (1.2V to 24V DC) with selectable voltage.

Switch Position Settings for Voltage Selection

Diagram and table showing switch settings for voltage selection.

4.4.3. Terminal Connector Overview

Terminal Connector Remarks and Notes

Notes on power supply terminals and various options.

Pulse Output Terminals (05-06)

Scaled Pulse Output Type OA

Active 24V DC pulse signal output.

Mechanical Relay Pulse Output Type OR

Mechanical relay output with specific power and frequency limits.

Passive Transistor Pulse Output Type OT

Passive transistor output.

PX Type Power Supply and Analog Output

PX Type Power Supply and Loop Power

Connecting external power for PX type or using 4-20mA loop.

Analog Output Types AA and AB

Standard analog output proportional to flowrate. Types AA and AB.

Analog Output Signal Options

Intrinsically Safe Analog Output Type AF

Floating 4-20mA signal for intrinsically safe applications.

Isolated Analog Output Type Al

Isolated 4-20mA signal output, usable with battery power.

Passive Analog Output Type AP

Passive 4-20mA signal output, loop powers the unit.

Active 0-10 VDC Analog Output Type AU

Active 0-10VDC signal output.

Terminal 09-11: Flowmeter Input Signals

Sine-Wave (Coil) Signal Input

Use with coil output flowmeters; two sensitivity levels.

NPN NPN-LP Pulse Signal Input

Use with NPN output flowmeters; includes low-pass filter option.

Pulse Signal Input Types

PNP PNP-LP Pulse Signal Input

Use with PNP output flowmeters; includes low-pass filter option.

Active Signal Input Types (8.1 V-12 V, 24 V)

Use with active signal sensors; explains detection levels and voltage options.

Reed-Switch and NAMUR Signal Inputs

Reed-Switch Signal Input

Use with reed-switch flowmeters; advises REED LP filter.

NAMUR Signal Input

Use with Namur signal flowmeters; requires external power supply.

External Reset Input (Terminal 12-13, Type IB)

Resets total with an external switch via a potential-free contact.

Communication and Backlight Options

Communication Options (Terminals 26-31)

RS232, RS485, TTL serial communication and computer control.

Backlight Option (Terminal 26-31)

Adjustable backlight option with power requirements.

5. Intrinsically Safe Applications

General Information and Safety Instructions

Safety precautions for intrinsically safe installations, IP protection, and ATEX/IECEx directives.

Specific Safety Instructions for IS Circuits

Precautions for preventing voltage/current addition and combined connections.

Intrinsically Safe Terminal Connectors

Enclosure Label Information

Shows type labels for intrinsically safe certified units.

Overview of Intrinsically Safe Terminals

Overview of terminal connectors for Intrinsically Safe applications (XI).

Unit Classification for Group IIC

Conditions for classifying the unit as group IIC.

Intrinsically Safe Analog Output and Power Supply

Intrinsically Safe Analog Output Type AF

Floating 4-20mA signal for intrinsically safe applications.

Intrinsically Safe Power Supply Type PD

Intrinsically Safe power supply and sensor supply options.

PD-XI Voltage Selection Switches

Diagram and table for selecting voltage via switches.

5.3. Intrinsically Safe Configuration Examples

IS Configuration Example 1 (IIBIIIC, IIC)

Example of intrinsically safe setup with specific components.

IS Configuration Example 2

5.4 Battery Replacement Instructions

Battery Safety Precautions

Warnings for handling batteries to prevent fire, explosion, or burns.

Hazardous Area Battery Safety

Use only certified batteries for hazardous areas.

6. Maintenance Procedures

General Maintenance Guidelines

Maintenance by trained personnel; precautions for humidity.

Factors Affecting Battery Life-Time

Factors influencing battery life-time.

Periodic Maintenance Checks

Regular checks for casing, wiring, accuracy, and battery status.

Product Repair Policy

Product cannot be repaired by user; requires manufacturer or agent.

Appendix A: Technical Specifications

General Technical Details

Display, enclosure, keys, painting, and mounting specifications.

Operating and Intrinsically Safe Temperatures

Operational and Intrinsically Safe temperature ranges.

Power Supply Options Summary

Details of various power supply types and their consumption.

Sensor Excitation and Input Signal Details

Flowmeter Input Signal Types and Parameters

Input signal types (P, A, U) and their parameters.

Low-Pass Filter Availability

Notes on the availability of a low-pass filter for pulse signals.

External Reset Option Details

Details on the external reset function.

Output Configurations and Communication

Analog Output Types and Functions

Analog output types (AA, AB, AF, Al, AP, AU) and their functions.

Switch Output Types (Pulse Outputs)

Pulse output types (OA, OR, OT).

Communication Options and Protocols

Communication protocols, speed, addressing, and types (CB, CH, CI, CT, CX).

Operational Mode Functions and Parameters

Operator Functions: Display and Reset

Total and flowrate display, clearing total.

Total Display Parameters

Digits, units, and decimals for total display.

Accumulated Total Display Parameters

Digits and units/decimals for accumulated total.

Flowrate Display Parameters

Digits, units, decimals, and time units for flowrate.

Appendix B: Problem Solving Guide

Troubleshooting Flowmeter Pulse Issues

Checks for no pulses or too many pulses.

Troubleshooting Output Functionality

Steps for analog output and pulse output not functioning.

Troubleshooting Flowrate Display Zero

Diagnosing zero flowrate display with active total.

Pass Code and Alarm Handling

Actions for unknown pass code and interpreting alarm codes.

Appendix C: Communication Variables

Total Communication Variables Overview

Variables for total measurement (unit, decimals, K-factor).

Flowrate Communication Variables Overview

Variables for flowrate measurement (unit, time, decimals, K-factor).

Configuration Variables Summary

Display and Power Management Variables

Variables for display function, LCD update, and battery mode.

Flowmeter, Analog, and Pulse Output Variables

Variables for flowmeter signal, analog output, and pulse output configuration.

Other Configuration Variables (Pass Code, Tag)

Variables for pass code, tag number, and other settings.

Communication Variables Details

Total, Accumulated Total, and Flowrate Communication

Details on reading/writing total, accumulated total, and flowrate via communication.