4.6.2 TERMINAL 03-04: PULSE OUTPUT R2
The function of this output is set in Setup menu 9 Pulse Output. The maximum pulse frequency of
this output is 500Hz. If a relay output option has been supplied, be sure that the output frequency
does not exceed 5Hz or else the life-time of the relay will be reduced significantly. For detailed
schematics see next paragraph.
4.6.3 TERMINAL 05-06: PULSE OUTPUT R1
The function of this output is set in Setup menu 9 Pulse Output. The maximum pulse frequency of
this output is 500Hz. If a relay output option has been supplied, be sure that the output frequency
does not exceed 5Hz or else the life-time of the relay will be reduced significantly.
Type OA
Two active 24V DC outputs are available with this option.
Max. driving capacity 50mA@24V per output. (Requires power supply type PD/PF/PM).
Fig. 14: Terminal connections - Active output (typical)
Type OR
A mechanical relay output is available with this option.
Max. switch power 240V 0,5A per output. (Requires power supply type PD/PF/PM). Be sure that the
output frequency does not exceed 5Hz, else the relay life time will be reduced significantly.
Fig. 15: Terminal connections - Mechanical relay output (typical)