The menu also provides the access to live values of
Energy as:
Active Energy (E
p
) Wh
Reactive Energy (E
Q
r) in varh
Apparent Energy (E
s
) in VAh
To display a trend chart of the last 7 minutes of Power
values:
1. Push (Live-Trend).
2. Use or the cursor keys to show the list of
available parameters.
3. Push (Reset) to clear the graph and restart.
Note
In the user interface, the term Fundamental is
sometimes shortened to “Fund.” or “h01.”
Logger
– In Logger mode, you can:
Configure a new logging session
Review the data of an ongoing logging session in
memory
Review the data of a completed logging session (as
long as no new session has been started)
Push and then (Logging Sessions) to review a
logging session.
Logging Session Setup
When no logging session is active, push to display the
Setup Summary screen for logging. This screen lists all
logging parameters such as:
Session name
Duration and optional recording date and time for
start/stop
Interval of the average calculation
Demand interval (not available for load studies)
Energy costs (not available for load studies)
Description

Table of Contents

Other manuals for Fluke 1736

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fluke 1736 and is the answer not in the manual?

Fluke 1736 Specifications

General IconGeneral
Product typeThree phase power measurement logger
Cable lock slot typeKensington
International Protection (IP) codeIP50
Operating altitude0 - 4000 m
Non-operating altitude0 - 12000 m
Storage temperature (T-T)-20 - 60 °C
Operating temperature (T-T)-10 - 50 °C
Operating relative humidity (H-H)10 - 95 %
Built-in displayYes
Display diagonal4.3 \
Touchscreen typeResistive
Display resolution480 x 272 pixels
Display technologyTFT
Efficiency68.2 %
Battery life4 h
Charging time6 h
Battery voltage3.7 V
Input frequency50/60 Hz
Battery capacity9.25 Wh
Power consumption (max)50 VA
Battery life (power save mode)5.5 h
Weight and Dimensions IconWeight and Dimensions
Depth55 mm
Width198 mm
Height167 mm
Weight1100 g
Power adapter weight400 g
Power supply dimensions (WxDxH)130 x 45 x 130 mm

Related product manuals