Power Logger
Electrical Specifications
67
Electrical Specifications
Power Supply
Voltage Range .................................................... nominal 100 V to 500 V (85 V min to 550 V max) using safety plug input
Mains Power ....................................................... nominal 100 V to 240 V (85 V min to 265 V max) using IEC 60320 C7 input (figure 8 power cord)
Power consumption ............................................ Maximum 50 VA (max. 15 VA when powered using IEC 60320 input)
Standby Power ................................................... <0.3 W only when powered using IEC 60320 input
Efficiency ............................................................ 68.2 % (in accordance with energy efficiency regulations)
Mains Frequency ................................................ 50/60 Hz ±15 %
Battery Power ..................................................... Li-ion 3.7 V, 9.25 Wh, customer-replaceable
On-Battery Runtime ............................................ Up to 4 hr (up to 5.5 hr in energy saving mode)
Charging Time .................................................... <6 hr
Voltage Inputs
Number of Inputs ................................................ 4 (3 phases and neutral)
Maximum Input Voltage ...................................... 1000 V
rms
(1700 V
pk
) phase to neutral
Input Impedance ................................................. 10 MΩ each phase to neutral
Bandwidth ........................................................... 42.5 Hz – 3.5 kHz
Scaling ................................................................ 1:1, variable
Current Inputs
Number of Inputs ................................................ 4, mode selected automatically for attached sensor
Current Sensor Output Voltage
Clamp ............................................................. 500 mV
rms
/ 50 mV
rms
; CF 2.8
Rogowski Coil ................................................. 150 mV
rms
/ 15 mV
rms
at 50 Hz, 180 mV
rms
/ 18 mV
rms
at 60 Hz; CF 4;
all at nominal probe range
Range ................................................................. 1 A to 150 A / 10 A to 1500 A with iFlex1500-12
3 A to 300 A / 30 A to 3000 A with iFlex3000-24
6 A to 600 A / 60 A to 6000 A with iFlex6000-36
40 mA to 4 A / 0.4 A to 40 A with 40 A clamp i40s-EL
Bandwidth ........................................................... 42.5 Hz – 3.5 kHz
Scaling ................................................................ 1:1, variable

Table of Contents

Other manuals for Fluke 1736

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fluke 1736 and is the answer not in the manual?

Fluke 1736 Specifications

General IconGeneral
Product typeThree phase power measurement logger
Cable lock slot typeKensington
International Protection (IP) codeIP50
Operating altitude0 - 4000 m
Non-operating altitude0 - 12000 m
Storage temperature (T-T)-20 - 60 °C
Operating temperature (T-T)-10 - 50 °C
Operating relative humidity (H-H)10 - 95 %
Built-in displayYes
Display diagonal4.3 \
Touchscreen typeResistive
Display resolution480 x 272 pixels
Display technologyTFT
Efficiency68.2 %
Battery life4 h
Charging time6 h
Battery voltage3.7 V
Input frequency50/60 Hz
Battery capacity9.25 Wh
Power consumption (max)50 VA
Battery life (power save mode)5.5 h
Weight and Dimensions IconWeight and Dimensions
Depth55 mm
Width198 mm
Height167 mm
Weight1100 g
Power adapter weight400 g
Power supply dimensions (WxDxH)130 x 45 x 130 mm