1736/1738
Users Manual
68
Auxiliary Inputs
Wired Connection
Number of Inputs ............................................ 2
Input Range .................................................... 0 V dc to ± 10 V dc
Wireless Connection (requires WiFi/BLE adapter USB1 FC)
Number of Inputs ............................................ 2
Supported Modules......................................... Fluke Connect 3000 series
Acquisition .......................................................... 1 reading/s
Scale factor ......................................................... Format: mx + b (Gain and offset) user configurable
Displayed units ................................................... User configurable (up to 8 characters, for example °C, psi, or m/s)
Data Acquisition
Resolution ........................................................... 16-bit synchronous sampling
Sampling Frequency ........................................... 10.24 kHz at 50/60 Hz, synchronized to mains frequency
Input Signal Frequency ....................................... 50/60 Hz (42.5 Hz to 69 Hz)
Wiring Configurations ......................................... 1-Φ, 1-Φ IT, Split phase, 3-Φ wye, 3-Φ wye IT, 3-Φ wye balanced, 3-Φ delta, 3-Φ Aron/Blondel (2-element
delta), 3-Φ delta open leg, 3-Φ high leg delta, 3-Φ delta balanced. Currents only (load studies)
Data Storage ....................................................... Internal flash memory (not user replaceable)
Memory Size ....................................................... Typical 10 logging sessions of 8 weeks with 1-minute intervals and 100 events The number of possible
logging sessions and logging period depends on user requirements.
Basic Interval
Measured Parameter .......................................... Voltage, Current, Aux, Frequency, THD V, THD A, Power, Power Factor, fundamental Power, DPF,
Energy
Averaging Interval ............................................... User selectable: 1 sec, 5 sec, 10 sec, 30 sec, 1 min, 5 min, 10 min, 15 min, 30 min
Total Harmonic Distortion ................................... THD for voltage and current is calculated on 25 harmonics
Averaging time min/max values
Voltage ............................................................ Full cycle RMS (20 ms at 50 Hz, 16.7 ms at 60 Hz)
Current ............................................................ Half cycle RMS (10 ms at 50 Hz, 8.3 ms at 60 Hz)
Aux, Power ..................................................... 200 ms
Demand Interval (Energy Meter Mode)
Measured Parameter .......................................... Energy (Wh, varh, VAh), PF, Maximum Demand, Cost of Energy
Averaging Interval ............................................... User selectable: 5 min, 10 min, 15 min, 20 min, 30 min, off

Table of Contents

Other manuals for Fluke 1736

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fluke 1736 and is the answer not in the manual?

Fluke 1736 Specifications

General IconGeneral
Product typeThree phase power measurement logger
Cable lock slot typeKensington
International Protection (IP) codeIP50
Operating altitude0 - 4000 m
Non-operating altitude0 - 12000 m
Storage temperature (T-T)-20 - 60 °C
Operating temperature (T-T)-10 - 50 °C
Operating relative humidity (H-H)10 - 95 %
Built-in displayYes
Display diagonal4.3 \
Touchscreen typeResistive
Display resolution480 x 272 pixels
Display technologyTFT
Efficiency68.2 %
Battery life4 h
Charging time6 h
Battery voltage3.7 V
Input frequency50/60 Hz
Battery capacity9.25 Wh
Power consumption (max)50 VA
Battery life (power save mode)5.5 h
Weight and Dimensions IconWeight and Dimensions
Depth55 mm
Width198 mm
Height167 mm
Weight1100 g
Power adapter weight400 g
Power supply dimensions (WxDxH)130 x 45 x 130 mm