EasyManuals Logo

Fluke 1736 User Manual

Fluke 1736
86 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #79 background imageLoading...
Page #79 background image
Power Logger
Electrical Specifications
69
Power Quality Measurements
Measured Parameter .......................................... Voltage, Frequency, Unbalance, Voltage Harmonics, THD V, Current Harmonics, THD A, and TDD
(requires IEEE519/Report license)
Averaging Interval ............................................... 10 min
Individual Harmonics .......................................... 2
nd
… 50
th
Total Harmonic Distortion ................................... Calculated on 50 harmonics
Events ................................................................. Voltage: Dips, Swells, Interruptions
Current: Inrush Current
Triggered Recordings ......................................... 1738 or 1736 with 1736/Upgrade license
Half cycle RMS of Voltage and Current
Waveform of Voltage and Current
Standards Compliance
Harmonics .......................................................... IEC 61000-4-7: Class 1
IEEE 519 (short time harmonics, requires IEEE519/Report license)
Power Quality ..................................................... IEC 61000-4-30 Class S, IEC62586-1 (PQI-S device)
Power ................................................................. IEEE 1459
Power Quality Compliance ................................. 1738 or 1736 with 1736/Upgrade license
EN50160 (for measured parameters)
Interfaces
USB-A ................................................................. File transfer via USB Flash Drive, Firmware updates, max. supply current: 120 mA
WiFi
Supported modes ........................................... Direct connection and connection to infrastructure (requires WiFi-Infrastructure license)
Security ........................................................... WPA2-AES with pre-shared key
Bluetooth ............................................................ read auxiliary measurement data from Fluke Connect 3000 series modules (requires WiFi/BLE adapter
USB1 FC)
USB-mini ............................................................ Data download device to PC
Extension port ..................................................... Accessories

Table of Contents

Other manuals for Fluke 1736

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fluke 1736 and is the answer not in the manual?

Fluke 1736 Specifications

General IconGeneral
Product typeThree phase power measurement logger
Cable lock slot typeKensington
International Protection (IP) codeIP50
Operating altitude0 - 4000 m
Non-operating altitude0 - 12000 m
Storage temperature (T-T)-20 - 60 °C
Operating temperature (T-T)-10 - 50 °C
Operating relative humidity (H-H)10 - 95 %
Built-in displayYes
Display diagonal4.3 \
Touchscreen typeResistive
Display resolution480 x 272 pixels
Display technologyTFT
Efficiency68.2 %
Battery life4 h
Charging time6 h
Battery voltage3.7 V
Input frequency50/60 Hz
Battery capacity9.25 Wh
Power consumption (max)50 VA
Battery life (power save mode)5.5 h
Weight and Dimensions IconWeight and Dimensions
Depth55 mm
Width198 mm
Height167 mm
Weight1100 g
Power adapter weight400 g
Power supply dimensions (WxDxH)130 x 45 x 130 mm

Related product manuals