2352 Walsh Ave. Santa Clara, CA 95051. U. S. A. Tel.: (408) 748-9100, Fax: (408) 748-9111 www.analogtechnologies.com
Copyrights 2000 – 2012, Analog Technologies, Inc. All Rights Reserved. Updated on 11/22/2012 3
nalog Technologies
317 and 319
Clamp Meter
Volts DC
Conforms to applicable European directives.
CAT Ⅲ
For measurements performed in the building installations such as distribution panels, feeders
and short branch circuits and lighting systems in large buildings.
Do not dispose of this product as unsorted municipal waste.
GENERAL SPECIFICATIONS
Table 2. Electrical Specifications
The accuracy specification is defined as ± (% reading+digits) at 23 ±℃ 5℃.
Function Parameter 317 319
(A ac)
Range
40.00A
600.0A
40.00A
600.0A
1000A
Resolution
0.01A
0.1A
0.01A
0.1A
1A
Accuracy
1.6%±6digit
(50-60Hz)
[40A]
2.5±8digit
(60-500Hz)
[40A]
1.5%±5digit
(50-60Hz)
[600A]
2.5±5digit
(60-500Hz)
[600A]
1.6%±6digit
(50-60Hz)
[40A]
2.5±8digit
(60-500Hz)
[40A]
1.5%±5digit
(50-60Hz)
[600A/1000A]
2.5±5digit
(60-500Hz)
[600A/1000A]
Crest factor add 2% into
spec for CF>2
3.0Max@500A
2.5Max@600A
3.0Max@500A
2.5Max@600A
1.4Max@1000A
AC response rms rms
( A dc)
Range
40.00A
600.0A
40.00A
600.0A
1000A
Resolution
0.01A
0.1A
0.01A
0.1A
1A
Accuracy
1.6%±6digit
[40A]
1.5%±5digit
[600A]
1.6%±6digit
[40A]
1.5%±5digit
[600A/1000A]
Range 600.0V