EasyManua.ls Logo

Fronius IG Plus USA - Technical Data; Field Adjustable Trip Points

Fronius IG Plus USA
29 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
18
Field adjustable trip points 208 V 240 V 277 V
Nominal AC output voltage, 208 240 277
Line-to-Line, [V]
Operating AC voltage range 183-229 211-264 -
default, Line-to-Line, [V]
Adjustment range for 105-248 121-287 -
voltage, Line-to-Line, [V]
Voltage trip limit accuracy, 1.0 1.0 -
Line-to-Line [% of nominal value]
Operating AC voltage range, 106-132 106-132 244-305
Line-to-Neutral, [V]
Adjustment range for voltage, 61-143 61-143 138-324
Line-to-Neutral, [V]
Adjustment range for voltage 0.016-4.25 0.016-4.25 0.016-4.25
clearing time [s]
Voltage trip limit accuracy, 1.0 1.0 1.0
Line-to-Neutral [% of nom. value]
Nominal output frequency [Hz] 60 60 60
Operating frequency 59.3-60.5 59.3-60.5 59.3-60.5
range [Hz]
Adjustment range for 57.0-60.48 57.0-60.48 57.0-60.48
frequency [Hz]
Adjustment range for frequency 0.016-300 0.016-300 0.016-300
clearing time [s]
Frequency trip limit accuracy [ms] 16.66
(1)
16.66
(1)
16.66
(1)
Detection time [ms] 25
(2)
25
(2)
25
(2)
Reconnect time default [s] 300 300 300
Adjustment range for reconnect 5-900 5-900 5-900
time [s]
(1)
16.66 ms are equivalent to 1 cycle
(2)
25 ms are equivalent to 1.5 cycles
Fronius IG
Plus
Technical Data