EN-US
746 One or more PC boards 
could not be found
1. PC boards not completely 
started
1. Wait 1 minute with the up-
date
2. PC boards not completely 
started
2. See device -> info menu: All 
versions available?
3. PC board data of some 
boards incompatible
3. Replace inverter
751 Real-time clock lost 1. Inverter has not had AC con-
nection for more than 5 days
1. Set time
2. Memory on Recerbo faulty 2. Replace Recerbo
754*–755* Time set 1. Time/date set
757 Time cannot be saved; in-
verter infeed is deactivated 
for safety reasons
1. Faulty real-time clock 1. Replace Recerbo
758 RTC quartz faulty in emer-
gency mode
1. Occurs once 1. Automatically corrected
2. Recerbo faulty 2. Recerbo faulty
760 System quartz faulty 1. Occurs once 1. Automatically corrected
2. Recerbo faulty 2. Replace Recerbo
761* Read error on on-board 
memory PC board
1. On-board memory PC board 
missing
1. Replace interface PC board 
with on-board memory PC 
board
2. Faulty ribbon cable 2. Replace ribbon cable
3. Recerbo faulty 3. Replace Recerbo
4. On-board memory PC board 
faulty
4. Replace inverter
762* Read error on memory PC 
board
1. Integrated memory PC 
board missing
1. Use/install original memory 
PC board
2. Faulty ribbon cable 2. Replace ribbon cable
3. Recerbo faulty 3. Replace Recerbo
4. Integrated memory PC 
board faulty
4. Replace inverter
763* Power limiter on on-board 
memory PC board cannot 
be read
1. On-board memory PC board 
missing
1. Use/install original memory 
PC board
2. Recerbo faulty 2. Replace Recerbo
3. On-board memory PC board 
faulty
3. Replace inverter
765* Recerbo cannot read power 
limiter
1. Recerbo faulty 1. Replace Recerbo
766 No power limiter found 1. Recerbo faulty 1. Replace Recerbo
2. On-board memory PC board 
or integrated memory PC 
board faulty
2. Replace inverter
767* Power limiter cannot be 
read
1. Occurs once 1. Automatically corrected
2. Recerbo faulty 2. Replace Recerbo
768 Power limiter changed 
during grid power feed op-
eration
1. Integrated memory PC 
board is connected or switched 
off during grid power feed op-
eration
1. Automatically corrected (sta-
tus code must be confirmed)
Code Description Behavior Remedy