Fronius Primo GEN24 3.0 / 3.0 Plus 3.6 / 3.6 Plus 4.0 / 4.0 Plus
Max. permitted mains impedance Z
max
on PCC
4)
None
Max. output fault current per period 29 A / 3 ms
AC output data PV Point
Max. output power 4133 W (for 5 s)
Nominal output power 3000 W
Nominal output current 13 A
Nominal grid voltage
1 ~ NPE 220 V / 230 V / 240 V
Nominal frequency
53 / 63 Hz
1)
Switchover time < 90 s
Power factor cos phi
2)
0 - 1
AC output data Full Backup
Max. output power 12400 W (for 5 s)
Max. output power (per phase) 4133 W (for 5 s)
Nominal output power 3000 W 3680 W 4000 W
Nominal output power (per phase)
7)
3680 W
Nominal output current (per phase) 16 A
Nominal grid voltage
3 ~ NPE 220 V / 380 V
3 ~ NPE 230 V / 400 V
Nominal frequency for Full Backup
53 / 63 Hz
1)
Switchover time < 90 s
Power factor cos phi
2)
0 - 1
General data
Maximum efficiency
97.6% 97.6% 97.6%
European efficiency (U
mpp nom
)
96.8% 97.0% 97.1%
European efficiency (U
mpp max
)
95.9% 96.3% 96.5%
European efficiency (U
mpp min
)
95.3% 95.6% 95.8%
Self-consumption at night
6.8 W
Cooling Controlled forced-air ventilation
Degree of protection IP 66
Dimensions H x W x D 528 × 474 × 163 mm
Weight 15.4 kg
Permissible ambient temperature -40 °C – +60 °C
Permissible humidity 0–100% (incl. condensation)
EMC device class B
DC / AC overvoltage category 2 / 3
Pollution degree
2