Technical data
Fronius Primo GEN24 3.0 / 3.0 Plus 3.6 / 3.6 Plus 4.0 / 4.0 Plus
DC input data
MPP voltage range
(at nominal output)
190 - 530 V 200 - 530 V 210 - 530 V
Max. input voltage
at 1000 W/m²/-10 °C in an open circuit
600 V
Min. input voltage 65 V
Feed-in start voltage 80 V
Feed-in start voltage in grid operation
5)
80 V
Max. input current (PV1 / PV2) 22.0 / 12.0 A
Max. short circuit current of solar modules (I
SC PV
) 33 / 18 A
Max. backfeed current
3)
33 / 18 A
Number of inputs - PV1 2
Number of inputs - PV2 2
DC input data battery
Max. voltage 455 V
Min. voltage 150 V
Max. current 22 A
Max. output
3000 W 3680 W 4000 W
DC inputs
1
DC overvoltage category
(in accordance with IEC 62109-1)
2
AC input/output data
Nominal output power (P
nom
) 3000 W 3680 W 4000 W
Max. output power 3000 W 3680 W 4000 W
Nominal grid voltage 1 ~ NPE 220V / 230V / 240 V
Min. grid voltage
155 V
1)
Max. grid voltage
270 V
1)
Max. output current 19.4 A 23.7 A 25.8 A
Starting current
6)
20 A / 1.3 ms
Nominal frequency
50 / 60 Hz
1)
Nominal frequency for Full Backup
53 / 63 Hz
1)
Total harmonic distortion < 3.5%
Power factor cos phi
2)
0.8-1 (adjustable)