In each of these programs, the solenoid valve opens for a time "ON 1" and closes for a time
"OFF 1". This process is repeated for the number of times specified under "Repeat". After
this number of repetitions has been completed, the process continues with the "ON 2" and
"OFF 2" times until charging is completed.
The following settings are available for temperature-controlled charging:
- automatic/OFF/required:
- automatic ... Temperature-dependent adjustment of the charging characteristic
- OFF ... The measured battery temperature is not taken into account
- required ...
Charging only starts when a temperature sensor is connected
- Error overtemperature ON/OFF:
- ON ... Error message in the event of battery overtemperature
Charging process stops and can only be continued once the battery has cooled
down and been reconnected
- OFF ... No error message in the event of battery overtemperature
- Warning overtemperature ON/OFF:
- ON ... Warning in the event of battery overtemperature
- OFF ... No battery overtemperature warning
Equalising charge:
- OFF:
There is no equalising charge.
- Delay:
If the battery remains connected to the charger for the duration of the equalising
charge delay ("equalize charge delay"), then a special type of charging takes place.
This prevents acid stratification.
The parameters for the current (ampere / 100 ampere hours), voltage (volt / cell) and
duration of the equalising charge can be changed.
- Weekday:
Specify the weekday on which the equalising charge is to take place.
The parameters for the current (ampere / 100 ampere hours), voltage (volt / cell) and
duration of the equalising charge can be changed.
- Manual equalising charge ("Manual"):
An equalising charge can be started manually by pressing the relevant key on the dis-
play. The equalising charge starts after a set delay time has been observed. The
charge parameters that have been set are followed. The parameters for the current
(ampere / 100 ampere hours), voltage (volt / cell) and duration of the equalising charge
may all be changed. This function is only available for Pb-Wet characteristics.
If a setting for the equalising charge is enabled, a symbol on the homescreen next to the
set ampere hours or charging time shows whether an equalising charge is being carried
out or can be started.
Temperature-controlled charging: