EasyManua.ls Logo

Fronius Symo GEN24 12.0 SC - Page 171

Fronius Symo GEN24 12.0 SC
200 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
AC output data PV Point / PV Point Comfort
Rated power 3000 W
Nominal output current 13 A
Nominal grid voltage 1 ~ NPE 220 V / 230 V / 240 V
Nominal frequency
53/63 Hz
1)
Switching time < 90 s
Power factor cos phi
2)
0 – 1
AC output data Full Backup
8)
Max. output power 12,765 W (for 5 s)
Max. output power (per phase) 4255 W (for 5 s)
Rated power 12,000 W
Rated power (per phase)
7)
4133 W
Nominal output current (per phase) 16 A
Nominal grid voltage 3 ~ NPE 220 V / 380 V
3 ~ NPE 230 V / 400 V
Nominal frequency for Full Backup
53/63 Hz
1)
Switching time < 90 s
Power factor cos phi
2)
0 – 1
General data
Maximum efficiency 98.3%
European efficiency (U
mpp nom
) 98.1%
European efficiency (U
mpp max
) 97.9%
European efficiency (U
mpp min
) 97.2%
Self-consumption at night ≤ 10 W
Cooling Controlled forced-air ventilation
Protection class IP 66
Dimensions H x W x D 595 × 529 × 180 mm
Weight 22.8 kg
Inverter topology Non-insulated transformerless
Permitted ambient temperature -25 °C – +60 °C
Permissible humidity 0 – 100% (incl. condensation)
EMC emission class
(according to IEC 6100062,
IEC 6100063)
B
DC/AC overvoltage category
(according to IEC 62109-1)
2 / 3
Pollution degree 2
Sound pressure 47 dB(A)
171

Table of Contents