Turn off the automatic circuit breaker.
Set the DC disconnector to the "Off"
switch position.
2
Loosen the 5 screws of the connection
area cover by rotating them 180° to
the left using a screwdriver (TX20).
Remove the connection area cover
from the device.
3
Press the lock on the back of the ter-
minal and remove the AC terminal.
Route the mains cable from below
through the cable gland on the right
side and the ferrite core.
IMPORTANT!
The ground conductor should not be
routed through the ferrite core, it
should be dimensioned longer and laid
in a loop to allow for movement so that
it is strained last in the event of failure
of the cable gland.
For more information on the cable
gland, see Cable diameter of the AC
cable on page66.