EasyManua.ls Logo

Fronius Symo GEN24 12.0 SC - Page 71

Fronius Symo GEN24 12.0 SC
200 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4
Strip the insulation of the single con-
ductors by 12 mm. Select the cable
cross section in accordance with the
instructions in Permissible cables for
the electrical connection on page 65.
Lift to open the terminal's operating
lever and insert the stripped single
conductor into the slot provided as far
as it will go. Then close the operating
lever until it engages.
IMPORTANT!
Only one conductor may be connected
to each pin. The AC cables can be con-
nected to the AC terminal without fer-
rules.
5
L1 Phase conductor
L2 Phase conductor
L3 Phase conductor
N Neutral conductor
PE Ground conductor
6
Insert the AC terminal into the AC slot
until it engages. Fasten the union nut
of the cable gland with a torque of
6 7 Nm.
71

Table of Contents

Related product manuals