Description
16
1.
Phase voltage
18
1.
Operating hours counter
2.
Neutral current
19
1.
Current
20
1.
Effective power
* Displayed when easy connection mode is activated (measurement = A).
This value indicates the total energy without considering the direction.
** Factory setting - displayed when drawn and delivered energy are meas-
ured separately (measurement = b).
Configuration
menu - structure
and parameters
Screen Code Description Values
PASS*** P1 Enter the current password 2633*
nPASS P2 Password change ** Four digits (0000-9999)
SYStEM P3 Type of system 3Pn*: three-phase system,
4-core
3P: three-phase system, 3-
core
2P: two-phase system, 3-
core
Ct rAtIo P4 Current transformer ratio from 1* to 1000
Ut rAtIo P5 Voltage transformer ratio from 1* to 1000
MEASurE P6 Measurement mode ** A: easy connection, meas-
ures all energy without tak-
ing the direction into ac-
count.
B*: measures imported and
exported energy separately.