Screen Code Description Values
InStALL P7 Connection check On: activated
Off*: deactivated
P int P8 Average power calculation
interval (minutes)
1* - 30
MOdE P9 Display mode ** Full*: full display
Easy: reduced display. The
values that are not dis-
played are still transmitted
via the serial interface.
tArIFF P10 Tariff management ** On: activated
Off*: deactivated
HoME P11 Screen showing measured
variables displayed at star-
tup and after 120 seconds
of inactivity **
For full display (Mode =
Full): 0* - 19
Ad-
drESS***
P14 Modbus address 1* - 247
bAUd P15 Baud rate (kBit/s) ** 9.6* / 19.2 / 38.4 / 57.6 /
115.2
PArITY P16 Parity ** Even/No*
STOP bit P16-
2
Only if parity = No. Stop bit.
**
1* / 2
rESET P17 Activation of the reset func-
tion for energy tariffs, max-
imum requested power and
part values of active and re-
active energy (the latter are
only transmitted via the
serial interface) **
No*: reset function deactiv-
ated.
Yes: reset function activ-
ated.
End P18 Returns to the measured
variables start screen
None
* Factory settings
** The settings can be protected by changing the default password (pass-
word cannot be reset).
*** Settings that need to be configured.
Setting the
transformation
ratio of the cur-
rent and voltage
transformers
Only the transformation ratio of the current and voltage transformers must be
set. All other parameters are preset at the factory.
Symbol Name Event Function
Up
1 x
Scroll one screen forward, increase the
value by 1
Down
1 x
Scroll one screen back, decrease the value
by 1
Enter
2 seconds
Call up settings, confirm value
34