Terminal Functions
Alarm signal will be output.
Data can be changed when this
function is not allocated.
L1/R, L2/S, L3/T
L1/L,
, L2/N
U, V, W
P(+), P1
P(+), N(-)
P(+), DB
G
Power input
Inverter output
For DC REACTOR
For DC bus connection
For EXTERNAL BRAKING RESISTOR
Grounding
Connect a three-phase power supply.
Connect a single-phase power supply. (
indicates the empty terminal.)
Connect a three-phase induction motor.
Connect the DC REACTOR.
Used for DC bus connection system.
Used for connection of the optional external BRAKING RESISTOR.
Ground terminal for inverter chassis
Three-phase 230V, 460V series
Single-phase 230V, 115V series
Wiring is required for the braking resistor built-in type.
Two terminals are provided.
Terminal Functions
13
11
C1
12
Potentiometer power supply
Common
Current input
Voltage input
(PID control)
(Frequency aux. setting)
(Inverse operation)
(PID control)
(For PTC thermistor)
(Frequency aux. setting)
(Inverse operation)
+10V DC power supply for frequency setting potentiometer (1 to 5kΩ)
0 to +10V DC / 0 to 100%
0 to +5V DC / 0 to 100% or +1 to +5V DC / 0 to 100% can be selected
by function setting.
+10 to +0V DC / 0 to 100% (switchable by digital input signal)
Used for reference signal (PID process command) or PID feedback signal.
Used for reference signal (PID process command) or PID feedback signal.
Used as additional auxiliary setting to various main settings of frequency.
+4 to +20mA DC / 0 to 100%
+20 to +4mA DC / 0 to 100% (switchable by digital input signal)
Connects PTC thermistor for motor protection.
Connect external resistor 1kΩ to terminal 13 - C1.
Used as additional auxiliary setting to various main settings of frequency.
Common for analog input/output signals (12, 13, C1)
Allowable maximum output current: 10mA
Input impedance: 22kΩ
Allowable maximum input voltage: 15V DC
If input voltage is +10V DC or over, the inverter
assumes it to be +10V DC.
Input impedance: 250Ω
Allowable maximum input current: +30mA DC
If input voltage is +20mA DC or over, the inverter assumes it to be +20mA DC.
Isolated from terminal CM and Y1E..
When FWD and REV are simultaneously ON,
the motor decelerates and stops. This function can
be set only for the terminals FWD and REV.
F18,
C32 to C34
E61
E61
F18,
C35 to C37
E62
H26, H27
E62
X1
X2
X3
FWD
REV
(HLD)
Digital input 1
Digital input 2
Digital input 3
Forward operation
command
Reverse operation
command
Forward operation
command
Reverse operation command
(FWD): ON… The motor runs in the forward direction.
(FWD): OFF…The motor decelerates and stops.
(REV): ON… The motor runs in the reverse direction. OFF…The motor decelerates and stops.
Multistep freq.
selection
2 (0, 1) different frequencies are selectable.
4 (0 to 3) different frequencies are selectable.
8 (0 to 7) different frequencies are selectable.
Frequency 0 indicates the frequency set by the keypad, built-in
potentiometer or analog signal.
ACC/DEC
time selection
(RT1): ON… ACC/DEC time 2 is effective.
(RT1): OFF…ACC/DEC time 1 is effective.
(BX): ON…The inverter output is shut off immediately and the motor will coast-to-stop.
Coast-to-stop command
Alarm reset
(RST): ON… Faults are reset.
(THR): OFF…The inverter output is shut off and the motor coasts-to-stop.
(JOG): ON… JOG frequency is effective.
(FWD):ON or (REV): ON…The inverter operates with JOG frequency.
Trip command (External fault)
Jogging operation
Freq. set 2/ Freq. set 1
(Hz2):ON or (Hz1): ON…Freq. set 2 is effective.
(WE-KP): ON… The function code data can be changed from the keypad.
(Hz/PID):
ON…The PID control is canceled, and frequency set
by multistep frequency, keypad or analog input.
(IVS): ON…Operation mode (normal operation/ inverse operation) can be changed.
(LE): ON…The link operation is effective. (RS-485 or Bus (Option))
(PID-RST): ON…PID integration and differentiation are reset.
(PID-HLD): ON…PID integration is temporarily stopped.
Used for 3-wire operation.
(HLD): ON… The inverter self-holds FWD or REV signal.
(HLD): OFF… The inverter releases self-holding.
Write enable for
KEYPAD
PID control cancel
Inverse mode changeover
Link enable (RS-485, Bus)
PID integral/differential reset
PID integral hold
3-wire operation stop
command
E01 to E03
Main circuitAnalog inputDigital input
Symbol Terminal name Functions Remarks
Related
function code
<ON state>
Source current: 2.5 to 5mA
(When input voltage is 0V)
Maximum input voltage: 2V
<OFF state>
Allowable maximum leakage current:
0.5mA
Maximum terminal voltage: 22 to 27V
(FWD)
(REV)
(SS1)
(SS2)
(SS4)
(RT1)
(BX)
(RST)
(THR)
(JOG)
(Hz2/Hz1)
(WE-KP)
(Hz/PID)
(IVS)
(LE)
(PID-RST)
(PID-HLD)
Switchable during ACC/DEC operation
No alarm signal will be output.
ON signal should be held for more than 0.1s.
E98, E99
C05 to C11
E10, E11
C20, H54
F01, C30
J01 to J06
F01, C30
H30, y99
PLC
CM
Connect to PLC output signal power supply. Common for 24V power (terminal P24).
Common for digital input signal.
PLC terminal
Common
+24V 50mA max.
Isolated from terminal 11 and Y1E.
The following functions can be set at terminals X1 to X3, FWD, and REV
for signal input.
(FWD and REV functions are factory-set at FWD and REV terminals,
respectively.
<Common function>
Sink/Source changeover function: Sink and source are changeable using
the built-in jumper switch.
Contact activation mode changeover function: ON timing can be
changed between short-circuit of terminals X1 and CM and open circuit
of them. The same setting is possible between CM and any of the
terminals among X2, X3, FWD
, and REV.
(SS1)
Digital input
(SS4)
Frequency
(SS2)
0
-
-
-
1
ON
-
-
2
-
-
ON
3
ON
-
ON
4
-
ON
-
5
ON
ON
-
6
-
ON
ON
7
ON
ON
ON
17