Option Guide
Option Guide
FunctionName
Surge absorber
Surge killer
Frequency meter
Option for single-phase
115V input
EMC compliance filter
AC REACTOR
(ACR)
Ferrite ring for
reducing radio noise
Filter capacitor
for reducing
radio interference
DC REACTOR
(DCR)
Displays the frequency in accordance with signals output from the inverter.
Braking resistor
[For improving input power-factor, reducing harmonics]
Used to reduce input harmonic current (correcting power-factor)
This makes communication to a PLC or personal computer system easy.
Frequency setting device
Frequency setting potentiometer (mounted externally)
Motor
M
Power supply
RST
UVW
L2/SL1/R L3/T
UVW
RST
UVW
P1
P
(+)
DB
MCCB
or
GFCI
Suppresses surges or noise invading from an external source, preventing malfunction from
magnetic contactors, control relays and timers, etc.
Absorbs surges or noise invading from an external source, preventing malfunction of electronic
equipment used in the switchboard.
Arrester
Suppresses induced lightning surges from power source, thus protecting all equipment
connected to the power source.
This is used in cases where a single-phase 115V power supply is used to feed a three-phase
230V inverter. (It can be applied to the inverter of 1HP or less.)
This is a dedicated filter which complies with the European EMC (Emission) Directive.
Used for power factor improvement and power supply coordination. However, it is
recommended that a DC REACTOR with
a higher efficiency and which is more compact and
lightweight be used. Use a DC
REACTOR (DCR) as a countermeasure for harmonics. If it is
necessary to supply a stabilized power supply, such as a DC bus system and running from that
(PN connection operation), please use such a reactor.
Reduces radio frequency noise. If the wiring between motor and inverter is shorter than 66ft (20m),
use the ferrite ring in the power supply side. If longer than 66ft (20m), use it in the output side.
Reduces noise.
For frequencies in the AM radio frequency band of 1MHz or less, a noise reduction effect can be
obtained. Absolutely never connect this device to the inverter’s output side.
[Use the DCR to normalize the power supply in the
following cases.]
1. The power transformer capacity is 500kVA or over and
exceeds the inverter rated capacity by 10 times.
2.
The inverter and a thyristor converter are connected
with the same transformer.
*Check if the thyristor converter uses a
commutation reactor. If not, AC reactor must
be connected to the power supply side.
3.
Overvoltage trip occurs due to open/close of the
phase-advancing capacitor for the power supply lines.
4.
The voltage unbalance exceeds 2%.
Output circuit filter
This filter is connected to the output circuit of inverters, and has the following functions:
1.
Suppressing fluctuation of motor terminal voltage
Protects the motor insulation from being damaged by surge voltage.
2.
Suppressing leakage current from output side wiring
Reduces the leakage current caused when several motors are operated in parallel or
connected with long wiring.
3.
Suppressing radiation noise or inductive noise from output side wiring
Effective noise suppression device for long wiring applications such as plant
* There are two kinds of filters for 460V series. Choose a desired one according to the purpose of use.
Extension cable
for remote operation
Used to connect the RS-485 communications card with the remote keypad, USB-RS-485
converter, etc.
Used to increase the braking capability when the motor needs to start and stop frequently or
when the moment of inertia is large.
Inverter support
loader software
Inverter support loader software, Windows based, that makes setting of function codes easy.
USB-RS-485
converter
Used to connect the RS-485 communications card with a USB port of your personal computer.
Attachments
Permit change of protective structure, replacement of Fuji's previous inverter model and
installation on the DIN rails, etc.
NEMA1 kit protects the inverter body with the structure that conforms to the NEMA1 standard
(approved as UL TYPE1).
RS-485 communications card
Used for the connector replacement of the copy adaptor.
Connector adaptor
NEMA1 kit
Prevents the motor insulation from being damaged by the surge current of the inverter.
Used when performing inverter remote operations with the remote keypad.Remote keypad
(IEC 61800-3 (5.2.3))
Voltage unbalance (%) = x 67
Max. voltage [V] – Min. Voltage [V]
Three-phase average voltage [V]
Magnetic
contactor
Inverter
Copy adaptor
Allows copying data to several inverters with easy connection to the inverter body.
Motor
DC
reactor
Inverter
M
Power transformer capacity
Thyristor
converter
Power-factor
correcting
capacitor
Commutation
reactor
Series
connected
reactor
25