Chapter 6: Function codes and application example
26
E29 Frequency arrival delay time
0.01 to 10.00 s
0.10
E30 Frequency Arrival (Hysteresis
width)
0.0 to 10.0 Hz
2.5
E31 Frequency
detection (FDT)
Detection level 0.0 to 400.0 Hz
50
E32 Hysteresis Width 0.0 to 400.0 Hz
1.0
E34 Level 0.00: Disable
Current value of 1% to 200% of the inverter rated current
100% of the motor
rated current
E35
Overload early
warning/Current
detection
Timer 0.01 to 600.00 s 10.00 s
E37 Level 0.00: Disable
Current value of 1 to 200% of the inverter rated current
100% of the motor
rated current
E38
Current Detection
2
Timer 0.01 to 600.0 s 10.00 s
E39 Coefficient of Constant Feeding Rate
Time
0.000 to 9.999 s
0.000
E40 PID display coefficient A -999 to 0.00 to 9990 100
E41 PID display coefficient B -999 to 0.00 to 9990 0.00
E42 LED display filter 0.0 to 5.0 s 0.5
0
E43 LED monitor Item selection 0: Speed monitor (Select by E48)
3: Output current
4: Output voltage
8: Calculated torque
9: Input power
10: PID process command (Final)
12: PID feedback value
13: Timer
14: PID output
15: Load factor
16: Motor output
21: Current position pulse count (position control)
22: Position deviation pulse count (position control)
E45 Item selection 0: Running status, rotational direction and operation guide
1: Bar charts for output frequency, current and calculated torque
0
E46 Language
selection
0: Japanese
1: English
2: Germany
3: French
4: Spanish
5: Italian
1
E47
LCD monitor
(only with multi-
functional keypad
TP-G1)
Contrast control 0 (Low) to 10 (High) 5
E48 LED monitor Speed monitor
item
0: Output frequency (Before slip compensation)
1: Output frequency (After slip compensation)
2: Reference frequency
3: Motor speed in r/min
4: Load shaft in r/min
5: Line speed in m/min
6: Constant feeding rate time
0
E50 Coefficient for speed indication 0.01 to 200.00 30.00
E51 Display coefficient for input
watt-hour data
0.000: (Cancel / reset)
0.001 to 9999
0.010
E52
Keypad (menu display mode) 0: Function code data editing mode (Menus #0 and #1)
1: Function code data check mode (Menus #2)
2: Full-menu mode (Menus #0 through #6)
0
E59 Terminal [C1] Signal Definition
(C1/V2 Function)
0 : Current input (C1 function), 4 to 20 mA DC)
1: Voltage input (V2 function), 0 to +10V DC )
0
E61 [12] 0
E62 [C1] 0
0
E63
Analogue input for
(Extension
function selection)
[V2]
Selecting function code data assigns the corresponding function to terminals [12], [C1] and
[V2] as listed below
0: None
1: Auxiliary frequency command 1
2: Auxiliary frequency command 2
3: PID process command 1
5: PID feedback value
E65 Reference Loss Detection
(Continuous running frequency)
0: Decelerate to stop
20 to 120 %
999: Disable
999
E98 Terminal [FWD] Function Selecting function code data assigns the corresponding function to terminals [FWD] and [REV]