2 - 88
Available PLC
Communication Setting
The recommended communication parameter setting of both PLC and POD is as follows.
For further information, refer to the TOSHIBA’s PLC manual.
PLC Transmission Parameter Setting
For specifying parameters in the T series PLC, use a T-series programmer and enter the following data in the
system information “7. COMPUTER LINK”.
Station No. 1
Baud rate 19200 BPS
Parity Odd
Data bit 8 bit
Stop bit 1 bit
TOSHIBA PLC
(T series)
30
Port 01
19200bps
Odd
8
Baud Rate
Parity
Trasmission
Code
Data Length
Stop Bit 1
Item Setting of PLC
1
19200bps
Odd
8
1
Comm. Parameter of POD
RS-422 [Wiring Diagram 1]
T seriesT Series
Select PLC Type
Wiring Diagram
PLC
30 TOSHIBA PLC

Table of Contents