2 - 112
42
KEYENCE PLC • 3
(KV / KZ series)
42 KEYENCE PLC 3
Wiring Diagram
PLC
KZ-10/16/24/40/80/300/350
(Program port direct connection)
KV Series
(Program port direct connection)
RS-232C [Wiring Diagram 1] or
Cable made by KEYENCE [OP-26487]
+Connector made by KEYENCE [OP-26485]
Select PLC Type
KZ/KV
Series CPU
KZ 24/300
CPU
KZ 10/24
CPU
RS-422 Cable made by KEYENCE [KZ-C20]
+Cable made by FUJI [ UG200C-M ]
KZ-24/300
(Program port direct connection)
KZ-10/24
(Program port direct connection)
RS-232C [Wiring Diagram 1] or
Cable made by KEYENCE [OP-26487]
+Connector made by KEYENCE [OP-26485]
KV 700
CPU
KZ 700
(Program port direct connection)
Even
Baud Rate
Parity
Transmission
Code
Data Length
Stop Bit
Item Setting of PLC
0Port
0
38400bps
8
1
Comm. Parameter of POD
38400bps
*
1
Even
Baud Rate
Parity
Transmission
Code
Data Length
Stop Bit
Item Setting of PLC
0Port
0
57600bps
8
1
Comm. Parameter of POD
57600bps
*
1
Available PLC
*
When using RS232C cable made by KEYENCE [OP-26487] , attach the D-sub 25 pins connecter
[OP-26485] to the modular jack on the POD side to communicate.
Communication Setting
KV series / KV 700 series CPU
The communication parameter setting of POD is done automatically.
KZ24/300 series CPU
*
1Maximum baud rate is 38400 bps.If 57600bps or 115000bps is selected, POD communicates with a PLC forcibly at 9600 bps.
KV10/24 series CPU
*
1Maximum baud rate is 38400 bps.If 57600bps or 115000bps is selected, POD communicates with a PLC forcibly at 9600 bps.
KV700 series CPU
*
1 Maximum baud rate is 57600 bps.
Even
Baud Rate
Parity
Transmission
Code
Data Length
Stop Bit
Item Setting of PLC
0Port
0
9600bps
8
1
Comm. Parameter of POD
9600bps
*
1