EasyManua.ls Logo

Fuji Electric UGx20 SERIES - Fuji Plc • 1

Fuji Electric UGx20 SERIES
275 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 - 1
1 FUJI PLC 1
1
FUJI PLC • 1
(MICREX-F series)
Available PLC
Communication Setting
The recommended communication parameter setting of both PLC and POD is as follows:
Switch Setting
MODE Switch: RS-232C: 1 RS-485: 3
RS-485 Port Setting SW: “0” for both x10, x1
RS-485 Terminal Resistor: ON
Character Switches
Port
Transmission
Control Mode
RS-232C
RS-422
0
19200bps
Even
7 (ASCII)
Baud Rate
Parity
Transmission
Code
Data Length
Stop Bit 1
Terminal Resistor at Receiver
Item Setting of PLC
0
19200bps
Even
7
1
Comm. Parameter of POD
Provided for RS-485
1 (Asynchronous non-protocol by command)(fixed)
3 (Asynchronous non-protocol by command)(fixed)
PLC
F70, F70S
NC1L-RS2
NC1L-RS4
FFU120B
FFK120A
RS-232C [Wiring Diagram 1]
RS-485 [Wiring Diagram 2]
RS-232C [Wiring Diagram 1]
RS-485 [Wiring Diagram 2]
Select PLC Type
MICREX-F
Series
F55 NV1L-RS2
RS-232C [Wiring Diagram 1]
F80H, F120H, F120S
F140S, F15xS
Wiring Diagram
Link Unit
8
No
7
6
ON
ON
ON
Setting Contents
Switch setting
Parity provided
Even
5
ON 7 bit
4
ON 1 bit
2
ON
3
1
ON
OFF
Same as POD
(normally 19200bps)

Table of Contents