2 - 9
4 FUJI PLC 4
Switch Setting
MODE Switch: RS-232C: 1 RS-485: 3
RS-485 Port Setting SW: “0” for both 10, 1
RS-485 Terminal Resistor: ON
Character Switches
Available Memory
*
The current values of the timer and counter are indicated with TN/CN for purposes of
convenience in the table above. (The actual value is T/C.)
Set the memory to the extent of the memory range of each PLC model.
Use TYPE number to assign indirect memory for macro programs.
Standard Memory TOYOTA Ver. TYPE Remarks
D(data register) D 0
W (link register) R 1
M(internal relay) M 2 WM as word device
L (latch relay) K 3 WL(WK) as word device
X (input relay) X 4 WX as word device
Y(output relay) Y 5 WY as word device
R (file register) W 6
TN (timer/current value) TN 7
*
CN (counter/current value) CN 8
*
T(timer/contact) T 9
C(counter/contact) C 10
WS (step relay) - 11
8
No
7
6
ON
ON
ON
Setting Contents
Switch setting
Parity provided
Even
5
ON 7 bit
4
ON 1 bit
2
ON
3
1
ON
OFF
Same as POD
(normally 19200bps)