(Not defrosted for 10 minutes)
Outdoor fan : OFF
Compressor speed : 0 rps
EEV :
AO*A72LALT : 480 or 500 pls
AO*A90LALT : 350 pls
4-way valve : OFF
Outdoor fan : OFF
Compressor speed
AO*A72LALT : 70~95rps
AO*A90LALT : 100rps
Heating operation start : Compressor ON
Compressor operation time has passed 15~20min.
or
High pressure sensor detects above 2.09MPaG.
Defrost end
01-17
Defrost start
3. Defrost Flow Chart
The defrosting shall proceed by the integrating operation time
and outdoor heat exchanger emperature as follows.
Compressor integrating
operation:
Over 22 minutes to
below 62 minutes
Outdoor
heat exchanger
temperature:
Below - 9°C
Compressor integrating
operation:
Over 35 minutes
Compressor
OFF count :
40 times
Outdoor
heat exchanger
temperature:
Below - 5°C
Compressor integrating
operation:
Over 105 minutes
Outdoor
heat exchanger
temperature:
Below - 1°C
(In case of 1st defrost)
(In case of 2nd and later defrost)
(Integrating defrost
(Constant monitoring)
Outdoor temp -
Outdoor heat exchanger
temperature:
Above 5 degC
Compressor integrating
operation:
Over 62 minutes
Outdoor
heat exchanger
temperature:
Below - 3°C
Defrost Indicator.
is displayed
on the wired RC
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ARC90LHTA and is the answer not in the manual?

Fujitsu ARC90LHTA Specifications

General IconGeneral
BrandFujitsu
ModelARC90LHTA
CategoryAir Conditioner
LanguageEnglish

Related product manuals