1-3. DRY OPERATION
1-3-1 INDOOR UNIT CONTROL
The compressor rotation speed shall change according to set temperature and room
temperature variation which the room temperature sensor of the indoor unit has detected
as shown in the Fig 3.
01-03
Room
temperature drops
Room
temperature rises
Compressor : ON
Ts+1.5 °C
Ts+0.5 °C
Compressor : OFF
( Fig.3 : Compressor Control based on Room Temperature )
Ts : Setting temperature
Compressor
ON
OFF
Indoor fan
DRY air flow
OFF
( Fig 4 : Indoor Fan Control )
10 30 60 360 120 360 120 10 30
(sec)
X zone
Y zone
( Table 3 : Compressor Rotational Speed Range )
AO* A72LALT
AO* A90LALT
X zone
Y zone
X zone
Y zone
42rps
0
47rps
0
S-Lo