Trouble shooting 24
INDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators: Detective details:
Forecast of Cause :
Indoor fan motor 1 drivers circuit error
Indoor fan motor 2 drivers circuit error
Indoor unit Power PCB
When a momentary power cut off.
When do not start fan motor.
1. External cause 2. Connection of connector failure 3. Power PCB failure
Check Point 3 : Replace Power supply PCB
If Check Point 1, 2 do not improve the symptom, replace Power PCB.
02-26
Refer to error code table.
OKOK
Check Point 2 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 1 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop : Check if there is a large load electric apparatus in the same circuit.
Momentary power failure : Check if there is a defective contact or leak current
in the power supply circuit.
Noise : Check if there is any equipment causing harmonic wave near electric line.
(Neon bulb or electric equipment that may cause harmonic wave)
Check the complete insulation of grounding.
OKOK