- 46 -
DUCT TYPE
ARGA30-60F
3) Room temperature sensor control for cooling
Depending on the installed environment, correction of the room temperature sensor may be re-
quired. Select the appropriate control setting according to the installed environment.
4) Auto restart
Enables or disables automatic restart after a power interruption.
NOTE: Auto restart is an emergency function such as for power outage etc. Do not attempt to use
this function in normal operation. Be sure to operate the unit by remote controller or external
device.
5) Room temperature sensor switching
(Only for wired remote controller)
When using the wired remote controller temperature sensor, change the setting to "Both" (01).
00: Sensor on the indoor unit is active.
01: Sensors on both indoor unit and wired remote controller are active.
NOTE: Remote controller sensor must be turned on by using the remote controller.
6) External input control
"Operation/Stop" mode or "Forced stop" mode can be selected.
7) Room temperature sensor switching (Aux.)
To use the temperature sensor on the wired remote controller only, change the setting to "Wired
remote controller" (01).
This function will only work if the function setting 42 is set at "Both" (01).
Function number Setting value Setting description Factory setting
30
00 Standard ♦
01 Lower control
02 Slightly higher control
03 Higher control
Function number Setting value Setting description Factory setting
40
00 Enable ♦
01 Disable
Function number Setting value Setting description Factory setting
42
00 Indoor unit ♦
01 Both
Function number Setting value Setting description Factory setting
46
00 Operation/Stop mode ♦
01 (Setting prohibited)
02 Forced stop mode
Function number Setting value Setting description Factory setting
48
00 Both ♦
01 Wired remote controller