- 72 -
OUTDOOR UNIT
AOGA30-60F
9. Electrical characteristics
*1: Maximum current is the total current of the indoor unit and the outdoor unit.
*2: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005. As
the regulations of wire size and circuit breaker differ in each country or region, select appropriate
devices complied to the regional standard.
*3: Limit voltage drop to less than 2%. If voltage drop is 2% or more, increase cable conductor size.
Model name AOGA30FBTAS AOGA36FRTAS AOGA45FRTAS AOGA60FRTAS
Power
supply
Voltage V 220—240 ~ 3N 380—415 ~
Frequency Hz 50
Max operating current *1 A 23.0 10.5 14.0 15.5
Starting current A 60 43 47 67
Wiring
spec. *2
Circuit breaker
current
A30 20
Earth leakage
breaker
mA 30 (0.1 sec or less)
Power cable
mm
2
3.5—4.0 2.5—4.0
Connection
cable *3
mm
2
1.5—2.5 1.0—2.5
Limited
wiring length
m31 51