- 67 -
OUTDOOR UNIT
AOGA30-60F
6. Additional charge calculation
6-1. Model: AOGA30FBTAS
Refrigerant charge
6-2. Models: AOGA36FRTAS and AOGA45FRTAS
Refrigerant charge
6-3. Model: AOGA60FRTAS
Refrigerant charge
Refrigerant type R410A
Factory charge amount g 2500
Total pipe length m 7.5 or less 10 20 30 (Max.)
20 g/m
Additional charge amount g 0 50 250 450
Refrigerant type R410A
Factory charge amount g 3400
Total pipe length m 20 or less 30 40 50 (Max.)
40 g/m
Additional charge amount g 0 400 800 1200
Refrigerant type R410A
Factory charge amount g 4300
Total pipe length m 20 or less 30 40 50 (Max.)
40 g/m
Additional charge amount g 0 400 800 1200