- 45 -
DUCT TYPE
ARGA30-60F
Contents of function setting
Each function setting listed in this section is adjustable in accordance with the installation environ-
ment.
NOTE: Setting will not be changed if invalid numbers or setting values are selected.
1) Filter sign
Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated
amount of dust in the air of the room.
If the indication is not required, select "No indication" (03).
2) Static pressure
Select the appropriate static pressure according to the installation conditions.
For 30 model
For 36, 45 model
For 60 model
Function no. Functions
1)
11
Filter sign
2)
21
Static pressure
3)
30
Room temperature sensor control for cooling
4)
40
Auto restart
5)
42
Room temperature sensor switching
6)
46
External input control
7)
48
Room temperature sensor switching (Aux.)
8)
60
Switching functions for external output terminal
Function number Setting value Setting description Factory setting
11
00 Standard (2,500 hours)
01 Long interval (4,400 hours)
02 Short interval (1,250 hours)
03 No indication ♦
Function number Setting value Setting description Factory setting
21
00 Normal (30 Pa) ♦
01 High static pressure 1 (60 Pa)
02 High static pressure 2 (90 Pa)
03 High static pressure 3 (120 Pa)
Function number Setting value Setting description Factory setting
21
00 Normal (60 Pa) ♦
01 Low static pressure (30 Pa)
02 High static pressure 1 (90 Pa)
03 High static pressure 2 (120 Pa)
Function number Setting value Setting description Factory setting
21
00 Normal (60P a) ♦
02 High static pressure 1 (100 Pa)
03 High static pressure 2 (130 Pa)
04 High static pressure 3 (160 Pa)