- 52 -
OUTDOOR UNIT
AOGA30-60F
Type
Cooling only
Model name AOGA36FRTAS AOGA45FRTAS AOGA60FRTAS
Power supply 3N 380—415 V ~ 50 Hz
Available voltage range 342—457 V
Starting current A434767
Fan
Airflow rate Cooling
m
3
/h
5700—6100
Type × Q'ty Propeller × 2
Motor output W 70 × 2
Sound pressure level *1 Cooling dB(A) 56—57
Heat exchanger type
Dimensions (H × W × D)
mm
1260 × 900 × 36.4 1260 × 900 × 39.9
Fin pitch 1.30
Rows × Stages 2 × 60 3 × 60
Pipe type Copper
Fin
Type (Material) Corrugate (Aluminum) Flat (Aluminum)
Surface treatment Corrosion resistance (Blue fin)
Compressor
Type × Q'ty Scroll × 1
Motor output W 2440 3190 3560
Refrigerant
Type R410A
Factory charge g 3400 4300
Refrigerant oil
Type POE
Amount
cm
3
1242
Enclosure
Material Steel
Color
Beige
Approximate color of MUNSELL 10YR7.5/1.0
Dimensions
(H × W × D)
Net
mm
1290 × 900 × 330
Gross 1430 × 1050 × 445
Weight
Net
kg
100 102 107
Gross 108 110 115
Connection pipe
Size
Liquid
mm (in)
Ø 9.52 (Ø 3/8)
Gas Ø 19.05 (Ø 3/4)
Method Flare
Pre-charge length
m
20
Max. length 50
Max. height difference 30
Operation range Cooling °C 21 to 52
NOTES:
Specifications are based on the following conditions:
– Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
– Pipe length: 7.5 m, Height difference: 0 m.
Protective function might work when using it outside the operation range.
*1: Sound pressure level
– Measured values in manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.